2 Unpacking and Installation

2.0

U

NPACKING

AND

I

NSTALLATION

2.1

Unpacking and Preliminary Inspection

1. Inspect the shipping crate(s) for damage or signs of mishandling before unpacking the unit.
2. Remove any securing bands and cardboard packing and inspect the unit for any obvious

shipping damages.

3. If any damage as a result of shipping is observed, immediately file a claim with the shipping

agency and forward a copy to your local Liebert sales representative.

2.2

Handling Considerations

Larger units are bolted to a shipping pallet to facilitate handling by forklift or pallet jack. Check

the size and weight. Refer to the cabinet data furnished with the unit. Typical size and weights

are referred to in Table 1.

2.3

Storage

The unit should be stored in a clean, dry environment. Storage temperature range is -55ºC to

+85ºC (-67ºF to +185ºF). Care should be taken to avoid condensation. All packing and shipping

materials should be left intact until the unit is ready for final installation. If the unit has been

stored for an extended period of time, the unit should be cleaned and carefully inspected before

placing into service.

2.4

Location Considerations

Environment—The unit is designed for operation indoors in ambient temperatures of -40°C to

+60ºC (-40ºF to +140ºF) with a relative humidity of 0% to 95% (non-condensing).
The unit is provided in an industrial use enclosure that is dust-tight and drip-tight. The unit

should not be installed in areas with excessive dust, corrosive vapors, flammable materials or

explosive atmospheres.
Audible Noise—The audible noise of the unit is less than 40 dBA at five feet, which allows its

placement in almost any room.
Service Clearances—Service clearance is needed only at the front of the unit. Thirty-six inches

(36 in or 914 mm) minimum is recommended.

2.4.1 Equipment Performance

For maximum system performance, the unit must be located as close to the protected circuit as

practical to minimize interconnecting wiring length.
For optimum transient surge protection, coordinated surge suppression should be applied at the

service entrance and all other electrical connections to the building (telephone, CATV, etc.), at

known surge generating loads within the building (large motors, arc welders, switched capacitors,

etc.), as well as at sensitive electronic loads (such as computers, electronic appliances, solid state

motor drives, etc.). For interconnected electronic loads (such as by way of data cabling), transient

surge suppression should also be applied to the interconnecting wiring (data cables).
Mounting—Unit is intended to be wall-mounted. Refer to Figure 1 or unit submittal drawings

for typical mounting dimensions and weight.

2.5

Door Closing Adjustments

If the surface on which the enclosure is mounted is not flat, the door may not open and close prop-

erly. Also, if heavy equipment is mounted on a large door, the door may sag slightly. If the top of

the door strikes the lip that extends around the body opening, place metal shims behind the

mounting foot that is located at the bottom of the enclosure and closest to the door hinge. Place

the shims between the mounting foot and the wall or mounting surface. Be sure all mounting

screws are tightened securely