Electrical Connections 5

Disconnect Switch—TVSS units must be connected to the load side of the main service discon-

nect, or load side of a protected circuit’s disconnecting means.
Interceptor II “SI” Models with an “R” designator in the part number, are equipped with an inter-

nal disconnect switch, that can be used to de-energize the unit’s transient surge suppressing com-

ponents for servicing.
Table 3

Voltage ratings and power source configurations

Source Configurations

Nominal Operating Voltage

Model Voltage

L-N

L-L

L-G

Code

Single Phase L-N 2W+G

120

N/A

120

120N

230

N/A

230

230N

277

N/A

277

277N

Single Phase L-L 2W+G

N/A

208

208

208L

N/A

240

240

240L

N/A

480

480

480L

Split Phase 3W+G

120

208-240

120

120S

230

400-460

230

230S

277

480-554

277

277S

Three Phase Delta 3W+G

N/A

208

208

208D

N/A

240

240

240D

N/A

480

480

480D

Three Phase Delta Hi-Leg 4 W+G

120

240

120

240H

240

480

240

480H

Three Phase Wye 4W+G

120

208

120

120Y

230

400

230

230Y

277

480

277

277Y

For other voltages or source configurations, consult factory.