4 Electrical Connections

3.0

E

LECTRICAL

C

ONNECTIONS

All electrical connections should be installed only by a qualified (licensed) electrician. All wiring

must comply with the National Electrical Code (NEC) and applicable local codes.

3.1

Voltage Ratings and Power Source Configurations

Before making connections to the unit, verify that the unit model number and nameplate voltage

rating are appropriate for connection to the intended power source. See Table 3 for voltage rating

applications with typical power source configurations.
Surge Voltage Ratings—To obtain the suppression voltage ratings (SVRs), as obtained by

Underwriters Laboratory, Incorporated, in accordance with the Standard for Safety, Transient

Voltage Surge Suppressors (TVSS), Standard 1449, Second Edition, dated August 15, 1996,

marked on this product, #2 AWG wire must be utilized to connect the unit to your facilities’ power

grid. Connections made with conductors other that #2 AWG may result in different SVRs.
Circuit Ampacity Limitations—Representative samples of this product have been investigated

by Underwriters Laboratories, Incorporated to withstand, without exposing live circuits or compo-

nents at system voltages and fault currents of up to 200,000 AIC, as described in the Standard for

Safety, Transient Voltage Surge Suppressor (TVSS), Standard 1449, Second Edition, dated

August 15, 1996.

3.2

Parallel Connection

(see Figures 2 and 3)

With parallel connection, the length of the wiring to the Transient Voltage Surge Suppressor (TVSS)

unit must be minimized for best performance. Wires should be as short and straight as possible.
To reduce the wiring impedance to surge currents, the phase, neutral (if required), and ground

conductors are recommended to be twisted together and routed in the same raceway (conduit).

Avoid any sharp bends in the conductors.
Wire Sizing—With parallel connection, the size of the wiring to the TVSS unit is independent of

the protected circuit’s ampacity. Suggested wire size based on the unit’s transient surge current

capabilities are show in the table below.

NEC Articles 280-21 and 22 require surge arrestor connecting conductors to be at least #14 copper

or #12 aluminum.
Overcurrent Protection—The TVSS unit conducts practically no current under normal opera-

tion and conducts only very short duration transient surge currents.
External overcurrent protection is not specifically required by NEC Article 280 nor is it desired

since it impedes the performance of the transient voltage surge suppressor. If fusing is required,

please consult factory for recommendations.

!

CAUTION
Verify that all power circuits are de-energized and locked out

before making electrical connections.

Table 2

Suggested wire and breaker size

Model Series

Outline Drawing

Wire Size

Breaker Size

SI016 –SI025 Wire Lugs

82010

8-1/0

40A

SI016 –SI025 Disconnect

82011

8-1/0

40A

S0320 –SI050 Wire Lugs

82012

4-1/0

80A

S0320 –SI050 Disconnect

82013

4-1/0

80A

SI060 –SI075 Wire Lugs

82014

4-1/0

80A

SI060 –SI075 Disconnect

82015

4-1/0

80A

SI100 Wire Lugs

82016

4-1/0

80A

SI100 Disconnect

82017

4-1/0

80A