Led power-up sequence, Leds led identification, Power sitegate-232 – Liebert 232 User Manual

Page 13: Rev. (08-july-98)

Advertising
background image

© 1996-98 Liebert Corporation

13

Rev. (08-JULY-98)

Figure 11: SiteGate-232 LED Identification

RUN LED

ERROR LED

CONDITION

2 flashes per

sec.

Off

All normal

2 flashes per

sec.

2 flashes per

sec.

5 minute auto-restart delay

after system error.

2 flashes per

sec.

On

Exec halted after frequent

system errors.

5 flashes per

sec.

On

Exec startup aborted, Boot is

running.

5 flashes per

sec.

Off

Firmware download is in

progress by Boot.

7 flashes per

sec

7 flashes per

sec.

Brownout recovery delay (10

seconds)

14 flashes per

sec.

14 flashes per

sec.

Brownout in progress (supply

voltage low)

LEDs

LED Identification

The SiteGate-232's LEDs are as follows (see Figure 11):

Power - indicates when power is on.

Run - blinks when the processor is running.

Error - lights when an error is detected.

CMnet Receive - lights when SiteGate-232 receives data from the CMnet.

CMnet Transmit - lights when SiteGate-232 transmits data over the CMnet.

Console 2 Receive (RX) - lights when Console 2 port receives data.

Console 2 Transmit (TX) - lights when Console 2 port transmits data.

Console 1 Receive (RX) - lights when Console 1 port receives data.

Console 1 Transmit (TX) - lights when Console 1 port transmits data.

Run
Error
CMnet Receive
Cmnet Transmit
Console 2 recieve
Console 2 transmit
Console 1 recieve
Console 1 transmit

Console
Por t

n/c

+10v

n/c

n/c

6

7

8

9

1

2

3

4

5

dcd

rx

tx

dtr

gnd

Power
Indicator

Power
Supply

Power
Switch

Tx
Rx

Cons ol e 2

Auxiliary
Device
Port

Optional Shield

Baud 156K

Baud 9600/38.4K

Access
port

Run
Error
CM net Rec ei ve
Cm net Trans mi t
Cons ole 2 reci eve
Cons ol e 2 transm i t
Cons ole 1 reci eve
Cons ol e 1 transm i t

For ma t
b utton

CM net baud 9600

Cons ol e 1 baud 9600
Cons ol e 2 baud 9600

38.4K
38.4K
38.4K

Opti ona l S hie ld

Net -

Net +

CMne t

co nn ec tion

Off

On

Gro und

24 V AC

Us e sin gle Cl ass 2

sou rc e o nl y

Cl as s 2

50 -6 0 Hz

2 4 VAC

0. 4 Am p

Us e c opp er

co nd uc to r on ly

POWER

SiteGate-232

Advertising