Liebert 232 User Manual

Page 17

Advertising
background image

© 1996-98 Liebert Corporation

17

Rev. (08-JULY-98)

Output character pacing? If set to YES, this parameter reduces CMnet transmission speed by 50%.

This may be necessary when operating at 38.4k baud with older modules on the same CMnet.

Delay before sending all replies (20 msec minimum) = 20 msec: The time in milliseconds to wait

before replying to CMnet commands. This is necessary to allow the sender time to shut off its

transmitter and prepare to receive the reply. If the reply comes too quickly, it may be missed.

Interpacket delay....... (20 msec minimum) = 20 msec: The delay time in milliseconds between

successive CMnet messages sent by this module. This allows all receiving modules time to take action

on each message.

Alternate interpacket delay... (40 msec minimum) = 40 msec: This parameter is the same as the

Normal interpacket delay parameter, except this delay is used between color update messages which

require more time for the receiving module to process.

CMnet Tuning Parameters

Time to wait before attempting intrusive grab: This is the time allowed after a grab request on a

console port for a non-intrusive grab to be successful before resorting to an intrusive grab. A non-

intrusive grab is when the SiteGate-232 takes control of the CMnet without sending a stream of “! !

! ! !...” characters. This can only be successful if the modules on the CMnet employ the “grabless”

token passing scheme. A non-intrusive grab is preferred over an intrusive grab because it is quicker

and non-disruptive.

Maximum number of intrusive grab attempts per request: If the non-intrusive grab is unsuccessful, the

SiteGate-232 will attempt this many intrusive grabs before giving up entirely and returning a negative

acknowledgment on the console port that requested the grab.

Grab Silence Time: The CMnet must be silent for at least this long after an intrusive grab attempt to

consider the grab successful.

Time to hold the token when the token wraps around: When the CMnet token is passed from the

module with the highest CM address to the SiteGate-232 (CM address #1), the SiteGate-232 will hold

the token for this amount of time before passing it to module #2. This is useful for reducing the rate of

time broadcasts on CMnets with low module counts, because the SiteGate-232 broadcasts the time

every time the CMnet token is passed to it.

Time to wait for each module to acknowledge the token: When the SiteGate-232 passes the CMnet

token to a module, it will wait this long for the module to acknowledge that the token was received

before skipping it and passing the token to the next module.

Maximum online time per successful grab: The amount of time any console port is allowed to be online

on the CMnet after each successful grab. If the online time expires, the console port will be

disconnected from the CMnet and the SiteGate-232 will restart the CMnet token.

Maximum monitor time per monitor request: The amount of time any console port is allowed to monitor

the CMnet after each monitor request. If the monitor time expires, the console will be disconnected

from the CMnet and an additional monitor request must be issued to continue monitoring.

Console Port Parameters

Modem installed on this console port = No: This enables the use of a modem on the console port.