Introduction, Specifications, Introduction specifications – Liebert 232 User Manual

Page 3: Power, Console ports, Cmnet port, Status indication, Temperature range, Humidity range, Cmnet connection

Advertising
background image

© 1996-98 Liebert Corporation

3

Rev. (08-JULY-98)

Introduction

The SiteGate-232 is part of the Liebert SiteScan gateway family and provides communications between

a workstation and a control module network (CMnet) consisting of fewer than 50 modules. The

SiteGate-232 provides two EIA-232 Console Ports for connecting a workstation and/or a modem. The

console ports are switch selectable for baud rates up to 38.4k bps.

Communication between the SiteGate-232 and the CMnet is provided through a EIA-485 port. The

SiteGate-232 does not have a Direct Network (DN) connection.

NOTE: You must use FB Link v2.7 or later in order to transfer to any module containing Exec 6.0 or

later.

Specifications

Power:

24 VAC ±10%, 50-60 Hz, 7.2 VA.

Console Ports:

(2) EIA-232 serial ports (D-sub 9-pin connector, and 5-pin pluggable screw terminal

block) switch selectable for 9600 or 38.4k bps.

CMnet Port:

EIA-485, twisted pair, 9600/38.4k bps, optically isolated. (156k bps to be supported

by a future version of the module driver).

Status Indication:

Visual (LED) status of EIA-232 communication, CMnet communication, running,

errors, and power.

Temperature Range:

0-130 °F (-17.8 to 54.4 °C).

Humidity Range:

10%-95% relative humidity, non condensing.

Memory:

1 MB FLASH memory for module driver storage and 1024 kB of battery backed RAM.

Figure 1: SiteGate-232 Module Dimensions and Layout

CM net baud 9600

Cons ol e 1 baud 9600
Cons ol e 2 baud 9600

38.4K
38.4K
38.4K

SiteGate-232

EIA-232
Console
Port 1

EIA-232
Console
Port 2

Auxiliary
Device
Port

CMnet
Baud Rate
Jumper

Access
Port

LEDs

6 1/4"

CMnet
Connection

1 5/8"

Addressing
Dip Switch

Manual Format
Button

7 1/8"

Power
Switch

1"

Console
Por t

n/c

+10v

n/c

n/c

6

7

8

9

1

2

3

4

5

dcd

rx

tx

dtr

gnd

Power
Indicator

Power
Supply

Power
Switch

Tx
Rx

Cons ole 2

Auxiliary
Device
Por t

Optional S hield

Baud 156K

Baud 9600/38.4K

Access
port

Run
Error
CM net Rec ei v e
Cm net Trans m it
Cons ole 2 reci eve
Cons ol e 2 transm it
Cons ole 1 reci eve
Cons ol e 1 transm it

For ma t
b utton

Opti ona l S hie ld

Net -

Net +

CMne t

co nn ec tion

Off

On

Gro und

24 V AC

Us e sin gle Cl ass 2

sou rc e o nl y

Cl as s 2

50 -6 0 Hz

2 4 VAC
0. 4 Am p

Us e c opp er

co nd uc to r on ly