LGM Module Driver Status

This is the overall module status.

Function Block Type: This the Module Driver's three-character filename.

Name: This is the name referring to the space or equipment used.

Line: The telephone line number used by the Function Block.

LG: Gateway module number used by the Function Block.

CM: Control Module number used by the Function Block.

FB: Function Block number used by the Function Block.

Flags: This identifies three flags which indicate the FB is "marked" because of certain conditions.

-

Indicates that the FB is not marked.

P

Indicates that there has been a change to the FBs parameter page which has not been

transferred to the module.

M

Indicates that memory transfer has failed for this Function Block.

ID:

This is an identification of up to eight characters (the first of which must be an

alphabetic character) assigned to each FB. Every FB in the system has a unique ID.

Tele: This indicates the telephone number for the FB's gateway module.

All Options: This is the only changeable parameter in the Header portion of the FB and toggles

between Y and N.

Y All parameters become visible even if they have not been defined.

N Only defined parameters are shown.

Type: This parameter indicates how often the Function Block has been made in Eikon. If this

parameter does not match the corresponding parameter in the module, all parameters are displayed in

yellow and cannot be changed. Also, parameters cannot be uploaded or transferred. Function Blocks

having mismatched type do not have their parameter written to configuration text when the

configuration text is updated. To correct this problem, download memory to the module. This

parameter is checked when the FB is first displayed and after a successful memory transfer. This

parameter is not related to the Version microblock in Eikon.

Ver: This is the parameter that indicates how many times the FB's parameters have been changed. If

the FB file in the computer does not match the FB which is transferred in the module, the Ver

parameter and the parameters which do not match are displayed in purple. To correct this problem,

either upload or transfer the parameters. This parameter is not related to the Version microblock in

Eikon.

Module Status

This is the overall module status and indicates if any of the following conditions exist:

Auto-Restart Delay: The system has just restarted after a System Error and the module will not start

GFB execution until the auto-restart delay (5 minutes) has timed out. This prevents equipment from

being short cycled in the event of repeated System Errors.