Lincoln Impringer Conveyor Oven 1000 User Manual

Page 21

Advertising
background image

Impinger I -–1000 Series Service Manual - Domestic

21

Air Pressure Switch

Check for 120 VAC on both sides of switch. If

voltage present on one side only, check for air tube

blockage. Adjust air switch. If above fails, replace

air pressure switch.

Transformer, 24 VAC

Check for 120 VAC to primary of transformer.

Check for 24 VAC from secondary of transformer. If

there is primary voltage, but no secondary voltage,

replace transformer.

(Model 1004 & 1005)

For oven models 1004 and 1005, there is a 1 Amp

fuse located between the 24 VAC output from the

transformer and the coil of the burner motor relay. If

there is 24 VAC output from the transformer, but no

burner motor relay action, check fuse and fuse

holder. Replace as necessary.

Burner Motor Relay

Delete burner motor relay refer to Section D, Page

34.

Burner Blower Motor

Check for 120 VAC supply to burner blower motor.

If 120 VAC is present and motor does not run,

replace motor. WITH POWER OFF: turn blower

wheel to check for locked rotor.

NOTE:

Centrifugal Switch of Burner

Blower Motor

Check for 24 VAC output from secondary of

transformer. If voltage is present, check for 24 VAC

at pin 6 and the ground bar on ignition control and

valve assembly. If the burner blower motor is

running and there is no voltage at pin 6 and the

ground bar on the ignition control valve, replace the

burner blower motor.

Ignition Control and Valve

Assembly

Check for 24 VAC supply to the ignition control and

valve assembly at pin 6 and the ground bar. If

voltage is present, check for 24 VAC across pin #1

and the ground bar (pilot valve). If voltage is not

present, replace electronic control package. If the

pilot valve is energized, check to see that the high

voltage ignitor circuit is also energized. To check,

disconnect the ignitor lead from the bottom of

ignition control. Place female terminal of ignitor

lead approximately 1/8" from terminal post on

ignition control. Spark should jump the 1/8" gap. If

no spark is present,

replace ignition control.

No Pilot

If the ignition control is supplied with 24 VAC, and

the pilot valve (internal to valve assembly) and

ignitor circuits are energized, visually check for pilot

flame. This may be done by opening the small

inspection door on the end of the burner, or by

opening the main oven door and looking under the

lower finger housings on the right side of the oven.

If no pilot flame is visible, check the following.

Pilot Shut-off Valve

Check to see that pilot shut-off valve is open (shut-

off valve is located between ignition control and

valve assembly and burner.)

Pilot Tube

Check for gas pressure at pilot tube. Disconnect

pilot tube at burner and connect manometer to pilot

tube. If no gas pressure is present, check for

blockage in pilot tube or pilot shut-off valve. If these

are clear, and there is gas supplied to the oven,

replace the ignition control and valve assembly.

For ovens with

Johnson Controls

Ignition Control

(For ovens with

Honeywell Ignition

control, See Pg. 21)

Pilot Orifice

If there is gas pressure at the pilot tube, check the

pilot orifice for obstructions. Replace as need

Burner Ignitor

Check the burner ignitor head for any obstructions,

also check for frayed or broken wire, any type of

damage to spark gap (.100 in. 2.5 m.m.) If there is

visible damage, replace ignitor assembly.

Advertising
This manual is related to the following products: