LG LSU120HE User Manual

Page 22

Advertising
background image

22 Room Air Conditioner

Wrap the insulation material around the
connecting portion.

• Overlap the connection pipe insulation material

and the indoor unit pipe insulation material. Bind
them together with vinyl tape so that there is no
gap.

Route the indoor tubing and the drain
hose to the required piping hole position.

Plastic bands

Insulation material

Connection pipe

Flare nut

Indoor unit tubing

Torque wrench

Spanner (fixed)

Vinyl tape(narrow)

Adhesive

Drain pipe

Indoor unit drain hose

• When extending the drain hose at the indoor

unit, install the drain pipe.

• Tighten the flare nut with a wrench.

For right rear piping

Connecting the pipings to the indoor unit
and drain hose to drain pipe.

• Put a couple drops of refrigerant oil on the face

of the flare before assembling taking care not to
add any contaminants.

• Align the center of the pipings and sufficiently

tighten the flare nut by hand.

Indoor unit tubing

Flare nut

Pipings

Drain hose

Ш6.35

1/4

1.8

Ш9.52

3/8

4.2

Ш12.7

1/2

5.5

Ш15.88

5/8

6.6

Outside diameter

mm

inch

Torque

Vinyl tape(narrow)

Connection
pipe

Connecting cable

Vinyl tape
(wide)

Wrap with vinyl tape

Indoor
unit pipe

Pipe

• Bundle the piping and drain hose together by

wrapping them with vinyl tape over the range
within which they fit into the rear piping housing
section.

Wrap with vinyl tape

Drain hose

Pipe

Vinyl tape(wide)

• Wrap the area which accommodates the rear piping

housing section with vinyl tape.

• Mount the clamp on the boss with a type "B"

screw.(SE-H/P: 9k, 12k C/O: 12k)

Drain hose

Clamp

Boss

Type "B" screw

Advertising
This manual is related to the following products: