Evacuation – LG LSU120HE User Manual

Page 48

Advertising
background image

48 Room Air Conditioner

Troubleshooting Guide

Evacuation

(All amount of refrigerant leaked)

• Procedure

(1) Connect the vacuum pump to the center

hose of charge set center hose

(2) Evacuation for approximately one hour.

– Confirm that the gauge needle has moved

toward -76 cmHg (vacuum of 4 mmHg or
less).

(3) Close the valve (Lo side) on the charge

set, turn off the vacuum pump, and con-
firm that the gauge needle does not move
(approxima-tely 5 minutes after turning off
the vacuum pump).

(4) Disconnect the charge hose from the vac-

uum pump.
– Vacuum pump oil.

If the vacuum pump oil becomes dirty or
depleted, replenish as needed.

Lo

Open

Open

Vacuum pump

3-Way
valve

Outdoor unit

Liquid side

Indoor unit

Gas side

3-Way
valve

CLOSE

OPEN

Use vacuum pump equipped with check value
applied to be prevented from flowing backward.