Connection of the cable, Notice – LG LSU120HE User Manual

Page 27

Advertising
background image

Service Manual 27

Connection Of The Cable

1

Indoor Unit

Outdoor Unit

2

3

4

1

2

3

4

5

6

G

To
branch
circuit

Ground

Power supply a

L1

*

L2

Connecting cable(Low voltage)

b

Terminal

(4P)

Terminal

(6P)

Outdoor unit

Wiring Diagram

Terminal block

Over 5mm

(0.2")

Cover control

Conduit panel

Connecting

cable

Power supply

cord

*

L1 is neutral for 115V models.

1. Remove the cover control from the unit

by loosening the 3 screws.

2. Dismount caps on the conduit panel.

3. Temporarily mount the conduit tubes

on the conduit panel.

4. Properly connect both the power sup-

ply and low voltage lines to the corre-
sponding terminals on the terminal
block.

5. Ground the unit in accordance with

local codes.

6. Be sure to size each wire allowing sev-

eral inches longer than the required
length for wiring.

7. Use lock nuts to secure the conduit

tubes.

1. shows field wiring.

2. Separately wire the high and low voltage line.

3. Use heat-proof electrical wiring capable of

withstanding temperatures up to 167°F.

4. Use outdoor and waterproof connection cable

rated more than 300V for the connection
between indoor and outdoor unit.
(For example, Type STOW)

• Be sure to comply with local codes while

running the wire from the indoor unit to
the outdoor unit(size of wire and wiring
method, etc).

• Every wire must be connected firmly.

• No wire should be allowed to touch refrig-

erant tubing, the compressor or any mov-
ing parts.

Connector trade size for this unit is 1/2" for
instructions on connecting depending on
the wire type you are using.

Power Supply

Model

Power source

9K

1ø, 115V

14

18

15A

12K

1ø, 115V

14

18

20A

18K

1ø, 230/208V

14

18

20A

24K

1ø, 230/208V

12

18

25A

AWG(MIN.)

Fuse or breaker

Capacity

NOTICE