Operation

15

5.0

O

PERATION

The Liebert LDM is a factory-installed option to provide monitoring of the main breaker, branch cir-

cuit breakers and subfeed breakers. It may be installed in the Liebert PPC Precision Power Center,

Liebert FDC, Liebert FPC and Liebert RDC Remote Distribution Cabinet.
Software available on Liebert’s Web site (see 5.3 - Downloading the Software) can be installed on a

desktop or laptop computer (PC) to monitor status and configure breaker parameters and alarm set-

points. These monitoring and configuration functions are described in 5.4 - Using the Monitor Tool

and 5.5 - Using the Configuration Tool.
The Liebert LDM monitors and displays the parameters listed in Table 5.

Circuit identification and status of each breaker are also displayed. Parameters are updated every

500msec.

Table 5

Parameters monitored for breakers

Parameters

Displayed and monitored for each:

Panelboard

branch

circuit breaker

Panelboard main

circuit breaker and

SqD I-Line panelboard

SqD I-Line

panelboard

circuit breaker

Subfeed

circuit

breaker

Voltage

Line-to-line

Line-to-neutral

Phase Current

Neutral Current

Ground Current

kVA

kW

kW-Hours

Percent Load

Power Factor

Crest Factor

Voltage Total Harmonic Distortion (THD)

Current Total Harmonic Distortion (THD)