Operation

21

5.5

Using the Configuration Tool

The Configuration tool allows users to set up breakers and view or change their parameters and

alarm setpoints.

5.5.1 Starting the Configuration Program

Before starting the Configuration tool, make sure you have the most recent version of the software

and decide whether you want to connect to the Liebert LDM or work in offline mode.
Offline mode allows you to run the configuration tool without being connected to the equipment.

(Prior to Version 25—LDM-Config-25—a service terminal connection was required to configure or

monitor the Liebert LDM.)

Proceed to 5.5.2 - Main Configuration Window Overview to begin configuration.
When a local connection to the Liebert LDM can be performed, load the configuration using the

instructions in 5.5.3 - Load a Configuration File from Disk.

NOTE
End users are unable to create a configuration file. Only Emerson Network Power technical

personnel can create a unique configuration file. Please contact your local Emerson Network

Power representative or call Liebert Services at 1-800-LIEBERT (1-800-543-2378) for

assistance.

NOTE
A configuration file is required for Offline Mode. If one is not available, connect to the

equipment locally and save the configuration to disk. See 5.5.4 - Install Configuration

Changes in the Unit and 5.5.5 - Save the Configuration File to Disk.

To Connect via COM Port

To Work in Offline Mode

1. If needed, download the latest version of the

software (see 5.3 - Downloading the

Software).

2. Connect a PC to the Liebert LDM via the external

DB9 connection. Refer to 5.2.1 - LDM Setup

Port Connection.

3. Run the file LDM-Config-xx.exe (where xx is

the version number) to start the Configuration

program.

4. In the Connect window, select the appropriate

COM port from the list of available ports.

5. Click Connect.

1. If needed, download the latest

version of the software (see 5.3 -

Downloading the Software).

2. Run the file LDM-Config-xx.exe

(where xx is the version number) to

start the Configuration program.

3. In the Connect window, click the

Work Offline button, shown below.

4. When prompted for the

configuration file, navigate to the

location of the file.

5. Click Open.