Operation

16

5.1

Alarms

The Liebert LDM constantly monitors configured parameters for normal values. When the unit

detects an alarm condition, it annunciates and displays alarm messages via the Monitor program (see

5.4 - Using the Monitor Tool).
Alarms must be manually reset after the alarm condition has been corrected and may be reset

through Modbus.
To facilitate troubleshooting:

• All alarms are stored in non-volatile memory to protect against erasure by a power outage.
• Alarms are saved in an event log. The event log stores up to 128 events using a first-in, first-out

format (FIFO).

All alarm thresholds for monitored parameters are adjustable by using the Configuration tool to

match site requirements (see 5.5 - Using the Configuration Tool).
Table 6 shows the types of alarms for the various types of breakers, along with a description, factory

default setpoints and allowable range for each.

Table 6

Alarm conditions and factory setpoints

Alarm

Description

Default setting

Range

Branch Breakers
• Overcurrent Warning

Current exceeds 75% of breaker amps

15A

0-75%

• Overcurrent Alarm

Current exceeds 80% of breaker amps

16A

10-80%

• Low Current Alarm

Minimum current level of a branch breaker

0%, which

disables

the alarm

0-70%

Panelboard Main Breaker and SqD I-Line Panelboard
• Phase Overcurrent Warning

Current exceeds 75% of breaker amps

170A

0-75%

• Phase Overcurrent Alarm

Current exceeds 80% of breaker amps

180A

10-80%

• Neutral Overcurrent Alarm

Current exceeds 95% of breaker amps

214A

10-200%

• Ground Overcurrent Alarm

Current exceeds 5 amps

5A

1-50A

• Overvoltage Alarm

At least one of the line-to-line voltages exceeds +6% of

nominal

0-50%

• Undervoltage Alarm

At least one of the line-to-line or line-to-neutral voltages

falls below -13% of nominal

0-50%

Subfeed Breakers and I-Line Output Breakers
• Phase Overcurrent Warning

Current exceeds 75% of breaker amps

170A

0-75%

• Phase Overcurrent Alarm

Current exceeds 80% of breaker amps

180A

10-80%

• Low Current Warning

Minimum current level of a branch breaker

0%, which

disables

the alarm

0-70%

• Neutral Overcurrent Alarm

Current exceeds 95% of breaker amps

214A

10-200%

• Ground Overcurrent Alarm

Current exceeds 5 amps

5A

1-50A

Summary Alarm

Detects and annunciates upon occurrence of any alarm

Panelboard Summary Alarm

Detects and annunciates upon occurrence of branch or

panelboard main breaker alarm