Installation, Controlling non-lincoln auxiliary equipment, Maxsa™ 10 controller – Lincoln Electric IM10023 User Manual

Page 13

Advertising
background image

A-6

INSTALLATION

MAXsa™ 10 CONTROLLER

A-6

S

W

IT

C

H

G

R

O

U

P

#

2

S

U

P

P

L

Y

3-PIN FLUX

RECEPTACLE

A

B

C

TERMINAL

STRIP

C

R

3

I

N

P

U

T

#

8

8

5

2

8

5

5

8

5

8

8

5

9

C

R

3

N

O

#

2

C

R

3

N

O

#

6

C

R

3

N

C

#

3

C

R

3

I

N

P

U

T

#

4

C

R

1

I

N

P

U

T

#

8

C

R

1

N

O

#

2

C

R

1

N

O

#

6

C

R

1

N

C

#

3

F

L

U

X

G

N

D

C

R

1

I

N

P

U

T

#

4

C

R

3

N

C

#

7

S

H

U

T

D

O

W

N

#

2

S

U

P

P

L

Y

S

H

U

T

D

O

W

N

#

1

S

H

U

T

D

O

W

N

#

1

S

U

P

P

L

Y

5

3

2

B

-4

9

S

W

IT

C

H

G

R

O

U

P

#

1

S

U

P

P

L

Y

S

T

A

R

T

F

L

U

X

F

IL

L

G

N

D

I

N

C

R

1

N

C

#

7

T

R

A

V

E

L

#

1

G

N

D

5

3

1

B

-4

8

4-PIN TRAVEL
RECEPTACLE

A

B

C

D

C

R

2

I

N

P

U

T

#

8

C

R

2

N

O

#

2

C

R

2

N

O

#

6

C

R

2

N

C

#

3

C

R

2

I

N

P

U

T

#

4

C

R

2

N

C

#

7

T

R

A

V

E

L

#

2

G

N

D

G

N

D

1

2

5

6

7

8

9

1

0

1

1

1

2

1

3

1

4

1

5

1

6

1

7

1

8

1

9

2

0

2

1

2

2

2

3

2

4

2

5

2

6

2

7

2

8

2

9

3

0

3

1

3

2

3

3

3

4

3

5

3

6

3

7

3

8

3

9

4

0

4

1

4

2

4

3

4

4

4

5

4

9

5

0

3

4

4

7

4

8

4

6

8

5

1

8

5

1

0

8

5

9

C

R

1

-4

C

R

1

-8

C

R

1

-2

C

R

1

-6

C

R

1

-3

C

R

1

-7

G

N

D

-B

C

R

3

-4

C

R

3

-8

C

R

3

-2

C

R

3

-6

C

R

3

-3

C

R

3

-7

G

N

D

-A

C

R

2

-4

C

R

2

-8

C

R

2

-2

C

R

2

-6

C

R

2

-3

C

R

2

-7

5

3

1

A

-4

8

5

3

2

A

-4

9

G

N

D

-C

8

5

1

1

S

H

U

T

D

O

W

N

#

2

8

5

3

8

5

6

8

5

7

S

T

O

P

IN

C

H

F

O

R

W

A

R

D

IN

C

H

R

E

V

E

R

S

E

Numbers Refer to

Relay Terminals

CR1, CR2 CR3

Relays

CONTROLLING NON-LINCOLN AUXILIARY

EQUIPMENT

Custom motion control and/or other auxiliary equipment

can be powered using the terminal strip and relays. To

use non-Lincoln motion control and/or flux hoppers, fol-

low instructions below. See Figure A.4.

1. Remove all input power to the MAXsa™ 10 CON-

TROLLER including any auxiliary power supplies.

2. Remove the wire duct cover to gain access to the

leads on the right side of the terminal strip.

3. Remove a plug button from one of the .875” (22.2mm)

access holes on the bottom of the MAXsa™ 10 CON-

TROLLER control box. Install a suitable strain relief to

protect the leads. See Figure A.1.

4. Remove the leads going from the terminal strip to the

corresponding connectors, i.e. terminal strip blocks

#11, #13, and #16 for the 4-pin TC-3 Travel Carriage

or terminal strip blocks #19, #20, and #23 for the 3-pin

Automatic Flux Hopper. See the Wiring Diagram.

5. These loose leads can be taped and secured in the

wire duct.

.

6. Any custom or non-Lincoln equipment can be powered

by the normally open contacts from relays CR1, CR2,

or CR3. The contacts for CR1 are connected to the

terminal strip blocks #3 through #8. The contacts for

CR2 are connected to terminal strip blocks #10

through #15. The contacts for CR3 are connected to

terminal strip blocks #17 through #22. See Figure A.3.

CR1 and CR2 relay coils are in parallel and are BOTH

turned ON and OFF as determined by the Travel Options

setting (P12 in the Set-up Menu) as long as the TRAVEL

MODE is set to AUTO. CR3 turns ON with the START

command and OFF with the STOP Command.

7. The supply voltage to power the devices is provided

by the end user. As shipped, the MAXsa™ 10 has the

auxiliary supply blocks (terminal strip blocks #48 and

#49) connected to the CR2 relay and CR3 relay

inputs, respectively. When the end user connects a

supply to the AUX blocks #48 and #49, this voltage will

be jumpered to the CR2 and CR3 relay inputs on ter-

minal strip blocks #11, #17, and #18.

NOTE: The CR1 relay is not connected to the AUX

terminal strip blocks; the customer must con-

nect power to this relay if it is to be used. See

relay ratings listed earlier.

8. Connect input supply voltage per the Auxiliary Input

Power Connection Instructions listed earlier.

9. The relays can also be used to provide contact closure

for any interfacing signals out using the normally open

contacts. An external auxiliary supply voltage would

not be necessary to use the relays as hard contact clo-

sure out signals.

NOTE: The CR1 relay as shipped does not have AUX

leads connected to it. This relay operates as

described above and has two normally open /

normally closed contacts that could be used as

a signal out when interfacing to PLC’s or cus-

tom controls.

FIGURE A.4 - CONTROLLING NON-LINCOLN EQUIPMENT

Advertising