Potterton Solar - Solar Thermal Domestic Hot Water System

12

3.0

Commissioning of solar controller

3.1.5 Menu “Info”

In this menu mode all measured values and operating

states are shown.

If the values are marked as “resettable”, they may be

reset in the following way:

Choose the value with buttons

and

Reset value by means of the button

Message “OK?” confirm with

= no or

= yes

Indication

Description

Reset possible

75ºC

Indication of current collector temperature

no

min. 12ºC

Indication of minimum collector temperature

yes

Re-settable to current temperature

max. 105ºC

Indication of maximum collector temperature

yes

Re-settable to current temperature

52ºC

Indication of current temperature storage tank (lower)

no

min. 40ºC

Indication of minimum temperature storage tank (lower)

yes

Re-settable to current temperature

max. 67ºC

Indication of maximum temperature storage tank (lower)

yes

Re-settable to current temperature

25ºC

Indication of universal temperature measuring points (T3)

no

55ºC

Indication of current temperature storage tank thermostat

no

60ºC

Indication of current temperature collector return

no

60ºC

Heating, cooling, temperature differential controller

no

heat source. Sensor T1...T6

35ºC

Temperature differential controller

no

heat target

1234 h

Operating hours for charging storage tank

Yes

Resettable to 0 h

927 kWh

Energy productivity for storage tank

Yes

Resettable to 0 kWh