Potterton Solar - Solar Thermal Domestic Hot Water System

24

4.0

Maintenance

4.1

Check heat transfer fluid

The heat transfer fluid must be checked every two years

with regard to its antifreeze and pH value.

- Check antifreeze using antifreeze tester.Target value is

approximately -21 deg C (40% concentration).

Do not allow to fall below 30% concentration.

If necessary replace or replenish the solar heat

transfer fluid.

- Check pH value with a pH indicator rod (target value

approx. pH 7.5). If the limit pH value is less than pH 7,

replace the heat transfer fluid.

4.2

Maintenance of the collector

The collector or the collector array must be inspected

visually, once a year, for any damage, leaks and

contamination.

4.3

Cylinder

Refer to manufacturers documentation.

% volume

Density at 20°C g/cu.cm

Refractive Index nD20

Frost protection °C

25

1.023

1.3627

-10

30

1.029

1.3690

-14

35

1.033

1.3747

-17

40

1.037

1.3801

-21

45

1.042

1.3855

-26

50

1.045

1.3910

-32

Solar fluid concentrations