RPO Installation

Installation of the RPO function must be carried out in compliance with
applicable regulations. The cable is not included.

In order to fully de−energize devices and the Powerware 9135 with the
RPO port, it is necessary to:

S

Use a two−position switch (normally−open or normally−closed contact
and held more than one second).

S

Connect this RPO switch to a device that trips all breaker(s) located
upstream

(1)

and downstream

(2)

the Powerware 9135 UPS. This can

be achieved by means of a shunt trip:

−

(1)

If not, the output devices could be powered again through static

switch when the two−position switch is released.

−

(2)

If not, the output devices will remain powered several seconds

after the RPO activation.

NOTE The internal batteries will remain connected to the power module after RPO
activation.

RPO Contact Normally−Open

RPO Contact Normally−Closed

5 Vdc to 27 Vdc

5 Vdc to 27 Vdc

RJ−12 (6p6c)

RJ−12 (6p6c)

Figure 19. RPO Communication Port

S

Signal:

−

Activation voltage: 5 Vdc to 27 Vdc

−

Current: 10 mA maximum