Features

Advertising
background image

FIELDPOINT

™

OPERATING INSTRUCTIONS

AND SPECIFICATIONS

FP-PWM-520 and
cFP-PWM-520

Eight-Channel, 5 V or 10–30 V PWM Output Module

These operating instructions describe how to install and use
the National Instruments FP-PWM-520 and cFP-PWM-520
pulse-width modulation modules (referred to inclusively as the
[c]FP-PWM-520). For details on configuring and accessing the
[c]FP-PWM-520 over a network, refer to the user manual for the
FieldPoint network module you are using.

Features

The [c]FP-PWM-520 is a FieldPoint pulse-width modulation
(PWM) output module with the following features:

•

Eight PWM sourcing output channels

•

0 to 100% duty-cycle capability with 12-bit resolution

•

Short-circuit protection for outputs

•

Outputs source 5 VDC or 10–30 VDC with user-provided
power supply

•

Independent configuration of the output period for each
channel from 1 to 65,535 ms in 1 ms increments

•

On/Off LED indicators

•

250 V

rms

CAT II continuous channel-to-ground isolation,

verified by 2,300 V

rms

, 5 s dielectric withstand test

•

–40 to 70 °C operation

•

Hot swappable