National Instruments NI 9264 User Manual
Page 14
Advertising

NI 9264 Operating Instructions and Specifications
14
ni.com
Protection
Overvoltage ................................ ±27 V at 25 °C
Short-circuit................................ Indefinitely
Update time
Noise ................................................. 500
μV
rms
Crosstalk ........................................... 90 dB
Settling time (100 pF load, to 1 LSB)
20 V step..................................... 20
μs
1 V step....................................... 15
μs
0.1 V step.................................... 13
μs
Number of
Channels
Update Time for
cRIO-9151 R Series
Expansion Chassis
Update Time for All
Other Chassis
1
3.7
μs min
3.1
μs min
2
6.6
μs min
5.3
μs min
3
9.4
μs min
7.5
μs min
16
47
μs min
37
μs min