Labview rt installation, Labview rt software installation, Labview rt installation -17 – National Instruments PXI/CompactPCI Embedded Computer NI PXI-8108 User Manual

Page 31: Labview rt software installation -17

Advertising
background image

Chapter 2

Installation and Configuration

© National Instruments Corporation

2-17

NI PXI-8108 User Manual

LabVIEW RT Installation

This section explains software installation and switch configuration for
LabVIEW RT on your PXI controller.

LabVIEW RT Software Installation

The following section describes the necessary steps to get your PXI
embedded controller setup to run LabVIEW Real-Time. In this section you
will configure the boot mode of the controller, verify or change IP settings,
and install LabVIEW Real-Time software.

Complete the following steps to install the LabVIEW RT software.

1.

Boot the NI PXI embedded controller into the real-time operating
system. Refer to the

LabVIEW RT Configuration Switches

section or

the

LabVIEW RT Options Setup Menu

section in this manual to

configure the controller for booting into LabVIEW RT.

The PXI controller will automatically boot into LabVIEW RT Safe
Mode when no software is installed. LabVIEW RT Safe Mode loads
with the basic real-time operating system and will automatically
attempt to connect to the network using DHCP. If DHCP is not
available, it will then connect to the network with a link-local
IP address.

Tip

You can connect a monitor to the desktop PC to display startup messages such as the

IP address and MAC address.

2.

Open Measurement & Automation Explorer (MAX) on another
computer in the same subnet and expand the Remote Systems branch.
MAX lists the PXI controller as the model name of the controller
followed by the MAC address (for example,
NI-PXI-8108 00802f108562).

3.

Click on the appropriate PXI controller entry to access the Network
Settings
tab in the right pane view.

4.

(Optional) Enter a name for the RT target in the Name text box.

5.

Set the network configuration options of the RT target in the
IP Settings section and click the Apply button.

For information about configuring network settings, refer to the
Configuring Network Settings book, accessible by browsing to
MAX Remote Systems Help»LabVIEW Real-Time Target
Configuration»Configuring Network Settings
from the Contents
tab of MAX Help.