I/O Protection

The NI 9478 provides protection against overcurrent and
short-circuit conditions.

Output Current Limit Thresholds

The NI 9478 provides two configurable current limit thresholds
for the module, Limit A and Limit B. The NI 9478 continuously
monitors the current through each output channel and detects if
the current exceeds either of the current limit thresholds. You can
configure the current limit thresholds and check the current limit
output status in software to determine if the current through each
channel has exceeded the current limit thresholds. Refer to the
software help for more information about configuring current
limits and checking output status. Visit

ni.com/info

and enter

cseriesdoc

for information about C Series documentation.

Overcurrent Protection

You can configure each channel on the NI 9478 to disable the
output if the current through the output exceeds either current
limit threshold. This protects the NI 9478 from overcurrent and
short-circuit conditions and provides a way to limit the current
through an external device.