Napco Security Technologies WI1501A User Manual

Page 27

Advertising
background image

L

NAPCO Security Systems

Freedom F-64 Installation Instructions

WI1501A 9/06



Page 27


Keypad Area Assignments
see Touchpad/Keypad Area Assignments

Keypad Jumpers
see keypad Installation Instructions

Keypad / Touchpad Features
The following programmed system features will activate only if they have also been enabled at the keypad.

Ambush

Easy Arming (required for Freedom Touchpads)

Touchpad (Police) Panic

Touchpad Auxiliary Panic

Touchpad Fire Panic


Keypad: F-64PROG Programmer and Gemini "K Series" Keypads
Panel automatically detects the Touchpads and keypads installed on the system. The F-64PROG Programmer is used for F-64 control
panel programming. Gemini "K Series" keypads may also be installed permanently in certain installations, such as installations that
comply with the Security Industry Association False Alarm Reduction Control Panel-01 Standard (SIA FAR CP-01). See page 38 for
more information.

Keypad Sounder on Alarm
see Touchpad/Keypad Sounder on Alarm

Keypad/Touchpad Panic
See Panic Zone

Keypad/Touchpad Tamper
See Tamper

Keyswitch Arming; Maintained-Key Input Arming
The area will arm/disarm when the programmed zone is momentarily shorted (momentary keyswitch). To supervise the keyswitch,
program the zone for Day Zone on Open. Keyswitch Arming will be reported as User 68. Keyswitch must be provided with EOL resistor.
Maintained-key input arming will arm when shorted and disarm when opened.

Line-Reversal Module, M278
The Line-Reversal Module allows the panel to be monitored by a central station through leased lines. On alarm, the module reverses
normal line-voltage polarity. For details, refer to the instructions furnished with the module.

Loop Response See Zone Response Time


Low Battery; Wireless Low Battery; Keyfob Low Battery
A low-battery system trouble will annunciate at the Touchpad/keypad when the battery terminal voltage drops below normal. This
condition may signal a local sounding device, report to a central station (program Panel Low Bat Report Code), or both. If a battery is
installed and low terminal voltage is detected, a restore will not occur until the battery is recharged to its specified level and passes a
dynamic test. The dynamic test may be initiated manually by pressing RESET, or it will be initiated automatically, every four hours, by
the panel. In wireless installations, when displaying RF transmitter status, a "LoBatt" indication denotes a low-battery condition at the
transmitter.

Lug E15 See "E" Lugs

Memory Failure
A User or Dealer Memory error will cause the sounder to pulse, the "

SYS/TRBL

" reminder to flash, and the display to read "

SYSTEM

TROUBLE/E19-00 SERVICE

" or "

SYSTEM TROUBLE/E20-00 SERVICE

". Press RESET to silence the sounder ("

SYSTEM READY

"

will display, along with the "SYS/TRBL" reminder). Activate RESET SYSTEM TROUBLE to manually reset the system trouble. A
Memory Failure can be programmed to activate an alarm output and/or report using its associated system Report Code.

Never Arm (Do not use for primary Burglary protection)
A zone programmed as "Never Arm" cannot go into alarm. If tripped, it will display at the Touchpad/keypad when the DISPLAY STATUS
function is selected. A chime will sound at the Touchpad/keypad while armed or disarmed if Chime is also programmed for that zone,
and enabled at the Touchpad/keypad. This feature is suggested for use as a garage-door or driveway monitor, or similar application.

No EOL Resistor
Program for any zone not wired with a 2200 Ohm end-of-line resistor. This will disable any zone-short indication (if programmed, "Day
Zone Short" is disabled). If not programmed, an end-of-line resistor must be installed. Note: This selection is automatically disabled for
zones selected as Fire. Note: Do not program for UL installations.

Glossar

y

Advertising