SPECIFICATIONS

Freedom F-64 Control Panel

O

perating Temperature: 0-49°C (32-120°F)

Input Power: 16.5-18.0 VAC via CLASS 2 Plug-In 20VA, 40VA or 50VA Transformer
Loop Voltage: 10-13Vdc
Loop Current: 3mA without Zone Doubling, 2.4mA with Zone Doubling using a 2.2K Ohm end-of-line resistor (Model EOL2.2K);

5mA for 2-wire smoke-detector zones; 1.4 mA using a 3.9K Ohm resistor (Model EOL3.9K) with Zone Doubling; 3mA with Se-
ries Zone with Loop Supervision
and 3mA with Series Zone Doubling with Loop Supervision

Loop Resistance: 300 Ohm max.; 50 Ohm for 2-wire smoke-detector zones
Alarm Voltage Output: 1
Programmable Negative Outputs: 2
Auxiliary Power Output: 11.7-12.5 VDC
Remote Power Output: 12 VDC regulated (for the F-64PROG programmer)
Combined Standby Current (Remote Power + Aux. Power + Fire Power): See following charts.





















NOTE:

(1)

Alarm current can be increased by reducing standby current by the same amount.

* Not evaluated by UL.

** Commercial Burglary specifications not evaluated by UL.

16.5VAC

TRANSFORMER

BATTERY

(12 VDC)

STANDBY
CURRENT

ALARM

CURRENT

STANDBY

TIME

40VA/50VA

7 AH

550 mA

450 mA

(1)

4 Hours

20VA*

7 AH

500 mA

2.0 A

4 Hours

20VA*

7 AH

500 mA

2.0 A

6 Hours

RESIDENTIAL BURGLARY & COMMERCIAL BURGLARY**

16.5VAC

TRANSFORMER

BATTERY

(12 VDC)

STANDBY
CURRENT

ALARM

CURRENT

STANDBY

TIME

40VA/50VA

7 AH

120 mA

520 mA

(1)

24 Hours

40VA/50VA *

Two 7 AH

360 mA

280 mA

(1)

24 Hours

20VA *

7 AH

120 mA

360 mA

(1)

24 Hours

20VA *

Two 7 AH

360 mA

120 mA

(1)

24 Hours

COMBINATION RESIDENTIAL FIRE & RESIDENTIAL BURGLARY

FOR ALL UL INSTALLATIONS

"ENABLE RESIDENTIAL FIRE" (ADDRESS 1422) MUST BE PROGRAMMED

The feature "Enable Residential Fire" (address 1422, option 4) must be programmed for ALL UL installations.

"DISABLE SYSTEM TROUBLE AUDIBLE TIMEOUT" (ADDRESS 2051) MUST BE PROGRAMMED

The feature "Disable System Trouble Audible Timeout" (address 2051, option 7) must be programmed for ALL UL
installations.



To program, please refer to the F-64 Programming Instructions (WI1502) for further information.

EZM Module: GEM-EZM4/8: Input, 50mA
Keypad Current: See keypad Installation Instructions.
Maximum Number of Keypads / Touchpads: 7
Maximum Wiring Length for each run (#22AWG): 1000' divided by total number of keypads /

Touchpads and EZMs on run

Keypad Dimensions: 4” x 5” x 1” (HWD); 11.1cm x 14.9cm x 2.7cm (HWD)