ENGINEERING DATA

THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE
The cross-flow heat recovery core transfers heat between the two airstreams.
It is easily removed for cleaning or service.
MOTORS AND BLOWERS
Each air stream has one centrifugal blower driven by a common PSC motor.
5 speed fan operation. 120 VAC, 1.4 Amps.

FILTERS - Washable air filters in exhaust and supply air streams.

MOUNTING THE HRV - Four threaded inserts at corners of case designed to
accept four reinforced polyester straps that are supplied with the unit.
DEFROST
Recirculating damper defrost system.
DEHUMIDISTAT
Adjustable Internal Dehumidistat.
CASE
Twenty gauge prepainted galvanized steel (G60) for superior corrosion resis-
tance. Insulated to prevent exterior condensation. Drain connections 2 - 1/2"
(12 mm) OD.
CONTROLS
ControlAir 15 - Standby/ON mode, 20 ON/ 40 OFF mode, Recirculation mode
(on compatible units), (each mode has 5 speeds). Control pad can be removed
from HRV and remotely mounted.

Weight 87 lbs. (39.5 kg) Shipping Weight 89 lbs. (40.5 kg)

PERFORMANCE

HVI CERTIFIED

Net supply airflow in cfm (L/s) against external static pressure

E.S.P

cfm

L/s

@ 0.1” (25 Pa)

196

(93)

@ 0.2” (50 Pa)

188

(89)

@ 0.3” (75 Pa)

178

(84)

@ 0.4” (100 Pa)

165

(78)

@ 0.5” (125 Pa)

149

(71)

Maximum Temperature Recovery

80%

Sensible Effectiveness
@ 117 cfm (55 L/s )

(CSA C439M)

72%

Sensible Efficiency
@ 117 cfm (55 L/s)

32

O

F (0°C)

64%

Sensible Efficiency
@ 67 cfm (31 L/s)

-13

O

F (-25°C)

70%

VAC @ 60HZ

120

WATTS / Low speed

74

WATTS / High speed

164

Amp rating

1.4

TOP VIEW

SIDE VIEW

25 1/2 "

(648 mm)

26 1/2"

(673 mm)

22 1/2"

(572 mm)

FRONT VIEW

ALL DUCT CONNECTIONS
ARE 6" (150 mm)

18"

(457 mm)

7 1/2"

(191 mm)

SUPPLY OF
FRESH AIR

FRESH AIR
SUPPLY
TO BUILDING

STALE AIR
RETURN FROM
BUILDING

STALE AIR
EXHAUST

DRAIN
CONNECTION

CONTROLS

*Service Clearance
25" (635 mm)

OPTIONS
99-104

Digital Electronic Timer - 20/40/60 min.

99-109

Air Sentry™ Air Quality Monitor designed to accept
remotely mounted Control Pad

99-250

Ventilation Dehumidistat - Dehumidistat designed to
accept remotely mounted Control Pad

99-163

Duct Heater w/ Electronic SCR Thermostat, 1 Kw, 6”
(150mm)

99-164

Duct Heater w/ Electronic SCR Thermostat, 2 Kw, 6”
(150mm)

99-186

Weatherhoods, Two - 6” (150mm) c/w 1/4” (6mm) mesh
screen

WARRANTY
Units carry a LIFETIME warranty on the heat recovery core and a 5
year replacement parts warranty.

TI-100-NE

0904

MAXTOP FANCURVE

200

150

175

75

50

100

125

25

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

Air Flo

w (cfm)

Static Pressure (inH

2

0)

HIGH SPEED

*

MEDIUM HIGH SPEED

MEDIUM SPEED

MEDIUM LOW SPEED

LOW SPEED

4

5

3

2

1

4

3

2

1

5

*

Manufacturers Data

Model MAXTOP

All units conform to
CSA and UL standards.

DIMENSIONS MAXTOP

inches (mm

)

Advertising