Model 200erv, Dimensions 200erv, Performance – Lifebreath 200MAX RX EN User Manual

Page 14: Engineering data

Advertising
background image

14

OPTIONS
99-104

Digital Electronic Timer - 20/40/60 min. (3 wire)

99-109

Air Sentry™ Air Quality Monitor designed to accept remote-

ly mounted Control Pad

99-186

Weatherhoods, Two - 6” (150mm) c/w 1/4” (6mm) mesh

screen

WARRANTY
Units carry a 5 year warranty on the energy recovery core and replace-
ment parts.

ERVs are not recommended for regions where the design temperature is
below 25°F (-4°C)

STALE AIR

TO OUTSIDE

FRESH AIR

FROM OUTSIDE

STALE AIR

FROM INSIDE

FRESH AIR

TO INSIDE

14

3

/

4

"

(375)

19"

(483)

*

All Duct Connections 6"(150mm)

FILTERS

BLOWERS

*NOTE: Front clearance
of 25 inches (635 mm)
is recommended
for ser vicing unit.

MOTOR

ENTHALPIC CORE

33-5/8"

(850)

BALANCING

DAMPER

BALANCING

DAMPER

Air Flo

w (cfm)

200ERV FANCURVE

200

175

150

125

100

75

50

25

0

0.3

0.4

0.5

0.6

0.7

0.8

0.9

Static Pressure (in H2O)

1.0

HIGH SPEED

*

MEDIUM HIGH SPEED

MEDIUM SPEED

MEDIUM LOW SPEED

LOW SPEED

4

5

3

2

1

5

4

3

2

1

?

*

Manufacturers Data

Model 200ERV

All units conform to
CSA and UL standards.

DIMENSIONS 200ERV

inches (mm

)

TI-98E

0805

PERFORMANCE

Net supply airflow in cfm (L/s) against external static pressure

E.S.P

cfm

L/s

@ 0.1” (25 Pa)

232

(109)

@ 0.2” (50 Pa)

223

(105)

@ 0.3” (75 Pa)

215

(102)

@ 0.4” (100 Pa)

195

(92)

@ 0.5” (125 Pa)

189

(89)

Sensible Effectiveness
@ 127 cfm (60 L/s)

(CSA C439M)

67%

Sensible Efficiency

32°F (0

O

C)

60%

Total Efficiency

55%

VAC @ 60HZ

120

WATTS / Low speed

87

ENGINEERING DATA

LATENT RECOVERY/MOISTURE TRANSFER CORE
The cross-flow energy recovery core transfers heat and water vapour
between the two airstreams. It is easily removed for cleaning or service.
MOTORS AND BLOWERS
Each air stream has one centrifugal blower driven by a common PSC
motor. 5 speed fan operation. High speed - 120 VAC.
FILTERS
Washable air filters in exhaust and supply air streams.
MOUNTING THE ERV
Four threaded inserts at corners of case designed to accept four PVC
reinforced polyester straps that are supplied with the unit.
CASE
Twenty gauge prepainted galvanized steel (G60) for superior corrosion
resistance. Insulated to prevent exterior condensation.
CONTROLS
ControlAir 15 - Standby/ON mode, 20 ON/ 40 OFF mode, Recirculation
mode (on compatible units), (each mode has 5 speeds). Control pad can
be removed from HRV and remotely mounted.

Weight 63 lbs. (28.7 kg)

Shipping Weight 65 lbs. (29.6 kg)