Attention, Model 155ecm, Performance – Lifebreath 200MAX RX EN User Manual

Page 7: Dimensions 155ecm, Engineering data

Advertising
background image

7

ENGINEERING DATA

THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE
The cross-flow heat recovery core transfers heat between the two
airstreams. It is easily removed for cleaning or service.
MOTORS AND BLOWERS
High effficiency electronic comutated ECM motor for maximum energy sav-
ings. Each air stream has one centrifugal blower. 5 speed fan operation
driven by one double shaft motor. 120 VAC, 1.0 Amps.
FILTERS
Washable air filters in exhaust and supply air streams.
MOUNTING THE HRV
Four threaded inserts at corners of case designed to accept four reinforced
polyester straps that are supplied with the unit.
DEFROST
Recirculating damper defrost system.
DEHUMIDISTAT
Adjustable Internal Dehumidistat.
CASE
Twenty gauge prepainted galvanized steel (G60) for superior corrosion resis-
tance. Insulated to prevent exterior condensation. Drain connections 2 -
1/2" (12 mm) OD.
CONTROLS
ControlAir 15 - Standby/ON mode, 20 ON/ 40 OFF mode, Recirculation
mode (on compatible units), (each mode has 5 speeds). Control pad can be
removed from HRV and remotely mounted.

Weight 71 lbs. (32.5 kg) Shipping Weight 73 lbs. (33.5 kg)

BALANCING DAMPER

33 5/8"

(850mm)

STALE AIR

FROM INSIDE

FRESH AIR

FROM OUTSIDE

STALE AIR

TO OUTSIDE

FRESH AIR

TO INSIDE

14 3/4"

(375)

19" (483)

*All Duct Connections 6" (150mm)

CONDENSATE DRAINS

FILTERS

BLOWERS

*NOTE: Front clearance of 25 inches (635 mm)
is recommended for servicing unit.

RECIRCULATING

DEFROST

DAMPER

MOTOR

CORE

OPTIONS
99-104

Digital Electronic Timer - 20/40/60 min.

99-109

Air Sentry™ Air Quality Monitor designed to accept
remotely mounted Control Pad

99-250

Ventilation Dehumidistat - Dehumidistat designed to
accept remotely mounted Control Pad.

99-163

Duct Heater w/ Electronic SCR Thermostat, 1 Kw, 6”
(150 mm)

99-164

Duct Heater w/ Electronic SCR Thermostat, 2 Kw, 6”
(150 mm)

99-186

Weatherhoods, Two - 6” (150 mm) c/w 1/4” (6 mm) mesh
screen

99-SILENCER6 6” dia. 16” long

WARRANTY
Units carry a LIFETIME warranty on the heat recovery core and a 5
year replacement parts warranty.

PERFORMANCE

Net supply airflow in cfm (L/s) against external static pressure

E.S.P

cfm

L/s

@ 0.1” (25 Pa)

163

(77)

@ 0.2” (50 Pa)

151

(71)

@ 0.3” (75 Pa)

140

(66)

@ 0.4” (100 Pa)

128

(60)

@ 0.5” (125 Pa)

115

(54)

@ 0.6” (150 Pa)

102

(48)

Maximum Temperature Recovery

83%

Sensible Effectiveness
@ 64 cfm (30 L/s)

(CSA C439M)

76%

Sensible Efficiency
@ 64 cfm (30 L/s)

32°F (0

O

C)

70%

Sensible Efficiency
@ 64 cfm (30 L/s)

-13°F (-25

O

C)

70%

VAC @ 60HZ

120

WATTS / Low speed

17

WATTS / High speed

95

Amp rating

1.0

DIMENSIONS 155ECM

inches (mm

)

Model 155ECM

All units conform to CSA
and UL standards.

The ECM motor produces a tone that some may
find objectionable. We recommend the
installation of the optional 99-SILENCER6 on the
‘Stale Air from Inside’ and ‘Fresh Air to Inside’
ducts.

ATTENTION

Air Flo

w (cfm)

155ECM FANCURVE

0.3

0.4

0.5

0.6

0.7

Static Pressure (in H2O)

?

*

Manufacturers Data

40

50

60

70

80

90

100

110

120

130

140

HIGH SPEED

*

MEDIUM HIGH SPEED

MEDIUM SPEED

MEDIUM LOW SPEED

LOW SPEED

4

5

3

2

1

5

4

3

2

1

Advertising
This manual is related to the following products: