Model 155max, Performance, Dimensions 155max – Lifebreath 200MAX RX EN User Manual

Page 6: Engineering data

Advertising
background image

6

ENGINEERING DATA

THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE
The cross-flow heat recovery core transfers heat between the two
airstreams. It is easily removed for cleaning or service.
MOTORS AND BLOWERS
Each air stream has one centrifugal blower driven by a common PSC motor.
5 speed fan operation. 120 VAC, 1.0 Amps.
FILTERS
Washable air filters in exhaust and supply air streams.
MOUNTING THE HRV
Four threaded inserts at corners of case designed to accept four reinforced
polyester straps that are supplied with the unit.
DEFROST
Recirculating damper defrost system.
DEHUMIDISTAT
Adjustable Internal Dehumidistat.
CASE
Twenty gauge prepainted galvanized steel (G60) for superior corrosion resis-
tance. Insulated to prevent exterior condensation. Drain connections 2 -
1/2" (12 mm) OD.
CONTROLS
ControlAir 15 - Standby/ON mode, 20 ON/ 40 OFF mode, Recirculation
mode (on compatible units), (each mode has 5 speeds). Control pad can be
removed from HRV and remotely mounted.

Weight 71 lbs. (32.5 kg) Shipping Weight 73 lbs. (33.5 kg)

BALANCING DAMPER

33 5/8"

(850mm)

STALE AIR

FROM INSIDE

FRESH AIR

FROM OUTSIDE

STALE AIR

TO OUTSIDE

FRESH AIR

TO INSIDE

14 3/4"

(375)

19" (483)

*All Duct Connections 6" (150mm)

CONDENSATE DRAINS

FILTERS

BLOWERS

*NOTE: Front clearance of 25 inches (635 mm)
is recommended for servicing unit.

RECIRCULATING

DEFROST

DAMPER

MOTOR

CORE

OPTIONS
99-104

Digital Electronic Timer - 20/40/60 min.

99-109

Air Sentry™ Air Quality Monitor designed to accept remotely
mounted Control Pad

99-250

Ventilation Dehumidistat - Dehumidistat designed to accept
remotely mounted Control Pad.

99-163

Duct Heater w/ Electronic SCR Thermostat, 1 Kw, 6” (150 mm)

99-164

Duct Heater w/ Electronic SCR Thermostat, 2 Kw, 6” (150 mm)

99-186

Weatherhoods, Two - 6” (150 mm) c/w 1/4” (6 mm) mesh screen

WARRANTY
Units carry a LIFETIME warranty on the heat recovery core and a 5 year
replacement parts warranty.

PERFORMANCE

HVI CERTIFIED

Net supply airflow in cfm (L/s) against external static pressure

E.S.P

cfm

L/s

@ 0.1” (25 Pa)

169

(80)

@ 0.2” (50 Pa)

161

(76)

@ 0.3” (75 Pa)

150

(71)

@ 0.4” (100 Pa)

130

(61)

@ 0.5” (125 Pa)

56

(26)

Maximum Temperature Recovery

83%

Sensible Effectiveness
@ 64 cfm (30 L/s)

(CSA C439M)

76%

Sensible Efficiency
@ 64 cfm (30 L/s)

32°F (0

O

C)

70%

Sensible Efficiency
@ 64 cfm (30 L/s)

-13°F (-25

O

C)

70%

VAC @ 60HZ

120

WATTS / Low speed

49

WATTS / High speed

120

Amp rating

1.0

TI-92-NE

0904

155MAX FANCURVE

175

150

125

100

75

50

25

0.1

0.2

0.3

0.4

0.5

0.6

0.7

Air Flo

w (cfm)

Static Pressure (inH

2

0)

HIGH SPEED

*

MEDIUM HIGH SPEED

MEDIUM SPEED

MEDIUM LOW SPEED

LOW SPEED

4

5

3

2

1

5

4

3

2

1

*

Manufacturers Data

DIMENSIONS 155MAX

inches (mm

)

Model 155MAX

All units conform to CSA
and UL standards.

Advertising
This manual is related to the following products: