Figure 1-3. scc-aixx signal connections – National Instruments Isolated Analog Input Modules SCC-AI14 User Manual

Page 6

Advertising
background image

SCC-AI Series Isolated Analog Input Modules

6

ni.com

Figure 1-3. SCC-AIXX Signal Connections

The inputs are designed in a floating (nonreferenced) single-ended
configuration. If the measured signals are floating, connect the negative
input pins, 1 and 3, to AISENSE on the SC-2345 terminal block through
a 10 k

Ω to 100 kΩ resistor. Figure 1-4 shows a floating signal connection

on one channel of the SCC-AIXX.

Figure 1-4. Nonreferenced Signal Connection for the SCC-AIXX (One Channel)

+

4

Lowpass

Filter

+

+

+

Lowpass

Filter

3

2

1

E Series DAQ Device

Signal

Source

ACH(

X )

SCC-AI

XX

AISENSE

AIGND

ACH(

X+8)

+

4

Lowpass

Filter

+

+

Lowpass

Filter

3

2

1

E Series DAQ Device

Signal

Source

ACH(

X )

SCC-AI

XX

AISENSE

AIGND

ACH(

X+8)

AISENSE
on SC-2345
terminal block

10

–100 k

Advertising