9

NI 9476 Operating Instructions and Specifications

Increasing Current Drive

Each channel has a continuous output current of 250 mA. If you
want to increase the output current to a device, you can connect
any number of channels together in parallel. For example, if you
want to drive 1 A of current, connect DO<0..3> in parallel as
shown in Figure 3. You must turn all parallel channels on and off
simultaneously so that the current on any single channel cannot
exceed the 250 mA rating.

Figure 3. Increasing the Current to a Device Connected to the NI 9476

NI 9476

250 mA

250 mA

250 mA

250 mA

DO3

DO1

DO0

DO2

1 A

+

_

Device

COM

External

Power

Supply

V

sup