6 type tests – RuggedCom RUGGED VDSL RS910L User Manual

Page 27

Advertising
background image

27

2007 RuggedCom Inc. All rights reserved

Rev100

6 Type Tests

6.1 IEC 61850-3 Type Tests

Test

Description

Test Levels

Severity

Levels

Enclosure Contact

+/- 8kV

4

IEC 61000-4-2

ESD

Enclosure Air

+/- 15kV

4

IEC 61000-4-3

Radiated RFI

Enclosure ports

20 V/m

x

Signal ports

+/- 4kV @ 2.5kHz

x

D.C. Power ports

+/- 4kV

4

A.C. Power ports

+/- 4kV

4

IEC 61000-4-4

Burst (Fast

Transient)

Earth ground ports

+/- 4kV

4

Signal ports

+/- 4kV line-to-earth, +/- 2kV line-to-

line

4

D.C. Power ports

+/- 2kV line-to-earth, +/- 1kV line-to-

line

3

IEC 61000-4-5

Surge

A.C. Power ports

+/- 4kV line-to-earth, +/- 2kV line-to-

line

4

Signal ports

10V

3

D.C Power ports

10V

3

A.C. Power ports

10V

3

IEC 61000-4-6

Induced

(Conducted) RFI

Earth ground ports

10V

3

IEC 61000-4-8

Magnetic Field

Enclosure ports

40 A/m continuous, 1000 A/m for 1 s

N/A

D.C. Power ports

30% for 0.1s, 60% for 0.1s, 100% for

0.05s

N/A

IEC 61000-4-29

30% for 1 period, 60% for 50 periods

N/A

IEC 61000-4-11

Voltage Dips &

Interrupts

A.C. Power ports

100% for 5 periods, 100% for 50

periods

2

N/A

Signal ports

2.5kV common, 1kV differential mode

@ 1MHz

3

D.C. Power ports

2.5kV common, 1kV differential mode

@ 1MHz

3

IEC 61000-4-12

Damped

Oscillatory

A.C. Power ports

2.5kV common, 1kV differential mode

@ 1MHz

3

Signal ports

30V Continuous, 300V for 1s

4

IEC 61000-4-16

Mains Frequency

Voltage

D.C. Power ports

30V Continuous, 300V for 1s

4

IEC 61000-4-17

Ripple on D.C.

Power Supply

D.C. Power ports

10%

3

Signal ports

2kVac (Fail-Safe Relay output)

N/A

D.C. Power ports

2kVac

N/A

IEC 60255-5

Dielectric

Strength

A.C. Power ports

2kVac

N/A

Signal ports

5kV (Fail-Safe Relay output)

N/A

D.C. Power ports

5kV

N/A

IEC 60255-5

H.V. Impulse

A.C. Power ports

5kV

N/A

Table 16 - IEC 61850-3 Type Tests