Water temperature sensor – Raypak B6000 User Manual

Page 10

Advertising
background image

WATER TEMPERATURE SENSOR

•

INSTALLATION
The water sensor
should be installed
in the system supply.

Multiple Boilers

Single Boiler

Water Sensor

TYPICAL WATER SENSOR

Water Temperature Sensor Installation Notes:

•

Locate sensor in system piping within a minimum of three (3) feet or prior to the first
take off connection, on the downstream side of the System Supply Loop.

•

Assure cable length does not exceed 4000 ft. Use larger gauge (Belden #9842) wire
if run is in excess of 100 ft.

•

Install in conduit with no other wiring.

•

Observe proper wire colors. Sensor is ploarity sensitive.

Page 10

Return

Supply