Raypak B6000 User Manual
Page 15

POWER TEST
CHECK POWER
Utilizing a Volt-Ohm-Meter (VOM) monitor the following on the "System Control Module"
and "Boiler Monitor(s)" for proper voltage levels.
POWER TEST TABLE
Module
Test Points
Indication
System Control
TB1-1- TB1-2
108 VAC to 132 VAC
System Control
TB1-1- TB1-3
108 VAC to 132 VAC
System Control
TB1-2- TB1-3
LESS THAN 1 VAC
System Control
TB1-1 - I
108 VAC to 132 VAC
System Control
TB1-2 - I
LESS THAN 1 VAC
System Control
TB1-3 - I
LESS THAN 0.5 VAC
Module
Test Points
Indication
Boiler Monitor
TB1-1- TB1-2
108 VAC to 132 VAC
Boiler Monitor
TB1-1- TB1-3
108 VAC to 132 VAC
Boiler Monitor
TB2-2- TB2-3
LESS THAN 1 VAC
Boiler Monitor
TB1 -1 - I
108 VAC to 132 VAC
Boiler Monitor
TB2 -2 - I
LESS THAN 1 VAC
Boiler Monitor
TB3 -3 - I
LESS THAN 0.5 VAC
FROM: BOILER MONITOR to SYSTEM CONTROL
Boiler Monitor
System Control
Indication
TB1 - 1
TB1 - 1
LESS THAN 0.5 VAC
TB1 - 2
TB1 - 2
LESS THAN 0.5 VAC
TB1 - 3
TB1 - 3
LESS THAN 0.5 VAC
TB1 - 2
TB1 - 3
LESS THAN 0.5 VAC
Page 15