Trouble Shooting Guide-Continued

Symptom

Boiler # x
"Not on Line" Displayed

Outdoor Temp. Sensor readings
are high.

Sensor reading 220°F.

Sensor reading - 35°F.

Low water cut-off alarm.

Power lamp off on Boiler Monitor.

Pump not running.

Off at flow switch.

Off on High Limit.

Corrective Action

Check primary power.
Correct as necessary.
Check communication cable,
check (surge) ground Remove /
Replace (R/R) as necessary.
Initialize system.

Refer to installation manual
mounting instructions. Possible
relocation for sensor.

Check sensor wiring for damage.
R/R as necessary.
Initialize system.

R/R as necessary
Initialize system.

Check power.
Check pump contactor / relay
R/R as necessary.
Replace F1 fusing.
Check main water supply

Replace F1 fusing.
Remove Relay-K1 to isolate circuit
loading.
R/R as necessary.
Reset circuit breaker.

Replace F1 fusing.

Check pump.
Reset circuit breaker

Check paddle on flow switch.
Check pump, contact or relay.
Replace F1 fusing.

Check and correct settings.
Meter amperage on pump.
R/R as needed.

Page 49

Possible Cause

Boiler not powered.

Outdoor sensor not mounted
correctly.

Sensor wiring shorted

Sensor wiring open.

Excessive circuit loading of pump
contacts by user supplied system
pump.
Low water level in boiler

Fuse F1 blown.
Excessive circuit loading of pump
contacts by user supplied system
pump.
Circuit breaker tripped.

Excessive circuit loading of pump
contacts by user supplied system
pump.

Pump going off on thermal over-
load circuit breaker tripped

Paddle damaged or missing.
Pump off on thermal overload.

Low limit settings.
Intermittent power or pump
failure.