Raypak B6000 User Manual
Page 39
Advertising

"ALTERNATE"
POWER TEST
CHECK POWER
Utilizing a Volt-Ohm-Meter (VOM) monitor the following on the "System Control" and "Boiler
Monitor(s)" for proper voltage levels. Check at the Terminal Block (TB).
POWER TEST TABLE
SYSTEM CONTROL
INDICATION
From:
To:
TB pin 1
TB pin 2
108 VAC to 132 VAC
TB pin 1
SPG
108 VAC to 132 VAC
TB pin 2
SPG
less than 1 VAC
BOILER
SYSTEM
MONITOR(S)
CONTROL
INDICATION
From:
To:
TB pin 1
TB pin 1
Less than 0.5 VAC
TB pin 2
TB pin 2
Less than 0.5 VAC
SPG
SPG
Less than 0.5 VAC
TB pin 2
SPG
Less than 0.5 VAC
BOILER MONITOR(S)
INDICATION
From:
To:
TB pin 1
TB pin 2
108 VAC to 132 VAC
TB pin 1
SPG
108 VAC to 132 VAC
TB pin 2
SPG
less than 1 VAC
END – – – – – – – –
"ALTERNATE"
Return to: "Boiler Monitor Select Switch"
(See page 20.)
Page 39
Advertising