AIR TEMPERATURE SENSOR

•

INSTALLATION

Fig. #9040

TYPICAL AIR TEMPERATURE SENSOR

Air Temperature Sensor Installation Notes:

•

Locate on coldest side of building, usually (North or West) side.

•

Install the sensor in a shaded area, out of direct sunlight.

•

Locate no higher than 2/3 way up side of building or between 2nd and 3rd floor if building
is more than 3 stories tall.

•

Shielded cable length not to exceed 4000 feet.

•

Do not locate under an overhang, near wall corners, near drafts from stacks, air
moving devices, windows, doors, or balconies.

•

Assure cable length does not exceed 4000 ft. Use larger gauge (Belden #9842)
cable if run is in excess of 100 ft.

•

Install in conduit with no other wiring.

•

Observe proper wire colors. Sensor is polarity sensitive.