Installation, Venting arrangements, Inst alla tion – Regency L900E-NG User Manual

Page 19

Advertising
background image

Regency

®

L900E Direct Vent Gas Fireplace

19

INST

ALLA

TION

VENTING ARRANGEMENTS

ALLOWABLE HORIZONTAL TERMINATIONS

The diagram shows all allowable combinations of vertical runs with horizontal terminations, using one 90

o

two 45

o

elbows equal one 90

o

elbow).

Note: Must use optional rigid pipe adapter (Part# 770-994) when using Rigid Pipe Venting Systems.

• Maintain clearances to combustibles as listed in "Clearances" section
• Horizontal vent must be supported every 3 feet.
• Firestops are required at each fl oor level and whenever passing through a wall.

A wall thimble is mandatory for all horizontal terminations due to high temperatures.

VENT RESTRICTOR SETTING:
Vent restrictor at 0" - factory set, no adjustment required unless otherwise indicated.
Refer to the "Vent Restrictor Position" section for details on how to change the vent restrictor to Set 1, Set 2 or Set 3 if required.

A vent guard is required when the AstroCap is installed above grade at 7 feet or lower.
A vent guard may also be required in other installations as per local codes, refer to "Exterior Vent Termination Requirements" section
for details.

Note: Regency

®

Direct Vent System (Flex) is only approved for horizontal terminations.

INSTALLATION

IMPORTANT NOTE

• The Simpson Dura-Vent and Selkirk Direct Temp horizontal termination caps
cannot be used in any applications.
• Only the AstroCap XL and Snorkels are certifi ed for horizontal terminations.

* A Vent Guard is required when the AstroCap
is installed above grade at 7 feet or lower.