Installation, Venting arrangements, Inst alla tion – Regency L900E-NG User Manual

Page 22: Allowable vertical terminations

Advertising
background image

Regency

®

L900E Direct Vent Gas Fireplace

22

INST

ALLA

TION

VENTING ARRANGEMENTS

ALLOWABLE VERTICAL TERMINATIONS

The shaded area in the diagram shows all allowable combinations of straight vertical and offset to vertical terminations, using two 90

o

elbows, with

Rigid Pipe Venting Systems for Propane and Natural Gas. Two 45

o

elbows equal to one 90

o

elbow. Maximum of four 45

o

elbows allowed.

• Vent must be supported at offsets.
• Firestops are required at each fl oor level and whenever passing through a wall.
• Maintain clearances to combustibles as listed in the "Clearances" section.

Refer to "Vent Restrictor Position" section for details on how to change the vent restrictor to Set 1, Set 2 or Set 3 if required.

Note: Must use optional fl ue adapter when using Rigid Pipe (Part # 770-994).