3.5 Pump Requirements

The pump is powered directly from the Variable
Frequency Drive (VFD). The VFD will be energized
via an output from the relay board switched through a
designated relay.

3.6 Variable Frequency Drive Requirements

The VFD must be powered separately from the
control enclosure. The 230 V drive power supply
must be 230 V, 50-60 Hz, 1 Ø. The 120V drive power
supply must be 120 V, 50-60 Hz, 1 Ø. The 480 drive
power supply must be 480 V, 50-60 Hz, 3 Ø. See
Page 19, Section 2.7 for additional details. The VFD
on/off switching is done by an output on the relay
board. The 0-10 V signal from the ULTRAVAC™
controller enclosure wired into VFD input relays 5 and
2 (

see Page 26, Figure 13 through Page 28, Figure

14) will dictate the speed of the pump. The VFD
output supply to the pump is 230 V 3 Ø 0-60 Hz for
115 V and 230 V models and is 480 V, 3 Ø, 0-60 Hz
for 480 V models. The frequency of the output supply
signal to the pump will be varied based on the 0-10 V
signal from the control enclosure. See

Page 21, Sec-

tion 3.2 for additional installation requirements.

FIGURE 10: Variable Frequency Drive Mounting

(Standard enclosures only, NEMA 4 enclosure
mounting varies by model)