2 altering vfd parameters – Roberts Gorden 10081601NA Rev H 12/11 User Manual

Page 49

Advertising
background image

SECTION 7: V

ARIABLE

F

REQUENCY

D

RIVE

P

ROGRAMMING

43 of 62

the password must be entered in order to access the
parameters again.

7.2 Altering VFD Parameters

Using the procedure described

on Page 42, Section

7.1.1 through Section 7.1.5, alter the following parame-
ters:

Parameter
Number

Parameter

Name

Factory

Default

New

Setting

P01

Line Voltage

01

01

P03

Start Method

01

05

P05

Standard

Speed

Source

01

(03) (0-10) Vdc

(04) (4-20) mA

P44

Password

225

Any #

000-999

P45

Speed at
Minimum

Signal

0.0Hz

Frequency

Setting noted

on Page 44,

Section 8.1.2

P46

Speed at

Maximum

Signal

60.0Hz

Frequency

Setting noted

on Page 44,

Section 8.1.2

Advertising