Figure 21: repeater external wiring – Roberts Gorden 10081601NA Rev H 12/11 User Manual

Page 42

Advertising
background image

ROBERTS GORDON

®

ULTRAVAC™ C

ONTROLLER

I

NSTALLATION

M

ANUAL

36 of 62

5.5.1 Repeater
If the RS-485 communications wire length is above 4000' (1219 m), a repeater must be used to extend the
signal. The repeater can also be used to install in different methods:

• To extend communications beyond the standard 4000' (1219 m) limitation.

See Page 36, Figure 21.

• To add parallel branches of ROBERTS GORDON

®

ULTRAVAC™ controller communications bus wiring.

See Page 37, Figure 22.

NOTE: The maximum number of ROBERTS GORDON

®

ULTRAVAC™ Controllers that can be installed is

242.

FIGURE 21: Repeater External Wiring

Description

Part Number

Repeater

URVRP