SECTION 5: C

OMMUNICATIONS

35 of 62

5.5 Communications Between Multiple ROBERTS GORDON

®

ULTRAVAC™ Controllers

If more than one ROBERTS GORDON

®

ULTRAVAC™ Controller is installed in a building, the
controllers’ RS-485 communications must be wired in
series.

See Page 35, Figure 20. Connect the

RS-485 terminal on controller

#

1 to the RS-485

terminal on controller

#

2 and so on in a daisy chain

fashion. For communication cable requirements,
See Page 22, Section 3.3

From a PC, by dialing into the modem on controller

#

1

or by connecting to controller

#

1 via RS-485

converter or TCP/IP communication module, the

system status and settings can be viewed for any of
the controllers on the network.

The control board identification dip switch must be
set on each ROBERTS GORDON

®

ULTRAVAC™

Controller.

See Page 35, Figure 20 for dip switch

settings. Contact Roberts-Gordon or your
ROBERTS GORDON

®

independent distributor, if

more than 20 controllers are connected.

FIGURE 20: Communications Between Multiple Controllers

Controller/Address

Number

Dip Switch Order (1,2,3,4,5,6,7,8)

Values (1=ON, 0=OFF)

11

11010000

12

00110000

13

10110000

14

01110000

15

11110000

16

00001000

17

10001000

18

01001000

19

11001000

20

00101000

Controller/Address

Number

Dip Switch Order (1,2,3,4,5,6,7,8)

Values (1=ON, 0=OFF)

1 (Central Controller)

10000000

2

01000000

3

11000000

4

00100000

5

10100000

6

01100000

7

11100000

8

00010000

9

10010000

10

01010000