Installation, Aeration settings – Regency IG34-LPG User Manual

Page 9

Advertising
background image

9

Regency IG34 Gas Inbuilt Fireplace

AERATION SETTINGS

The burner aeration is factory set but may need adjusting due to either the local gas supply, air supply or altitude. This adjustment is performed by
the installer. (Close the aeration for a more yellow fl ame, or open it to make the fl ame bluer).
NG: 13mm

open

LPG: 13mm

open

ULPG:

13mm

open

Note: Any damage due to carboning resulting from improperly setting the aeration and restrictor setting controls is NOT covered

under warranty.

INSTALLATION

IG34-NG: For 0 to 610 meters altitude
IG34-LPG: For 0 to 610 meters altitude
IG34-ULPG: For 0 to 610 meters altitude

Burner Inlet Orifi ce Sizes:
NG

LPG ULPG

Burner

#37

#52 #53

Max. Input
NG

31.7

mj

LPG

30.6

mj

ULPG

26.4

mj

Min. Input
NG

21.1

mj

LPG

25.1

mj

ULPG

20.9

mj


Supply Pressure
NG

1.13

kPa

LPG

2.75

kPa

ULPG

2.75

kPa

Manifold Pressure HIGH LOW

NG

0.87 kPa 0.4kPa

LPG

2.51 kPa 1.6kPa

ULPG

2.51 kPa 1.6kPa

Electrical: 240 V. 50Hz.
Circulation: High/Off/LO speed fan,

150/89 CFM.

Log Set: Ceramic fi ber, 7 per set.

Aeration Setting
NG

13mm open

LPG 13mm open
ULPG 13mm open

System Data

IG34

Advertising