EtherNet/IP parameters

Title

Communi

cation No.

Function Description

Factory

setting

c536

C536 EtherNet

Error

Monitor of the EtherNet error.
0: No error/clear error
1: Modbus TCP IO Scanning timeout
2: Network overload
3: Loss of Ethernet carrier

-

c554

C554

Web service (*3)

Enables web server.
0: Disable
1: Enable

1

c555

C555 Drive

Status

Monitor the inverter status.
3: Gate Block
4: Run
23: Fault

-

Modbus TCP parameters

Title

Communi

cation No.

Function Description

Factory

setting

c600-

c603

C600-

C603

IP Master (*3)

The IP address for PLC(Master) of the Modbus TCP.

0.0.0.0

c604

C604

IO Scan active (*3)

Enables IO Scan function.
0: Non-active
1: Active

0

(*3): This parameter is effective by reset. Please reset (power supply reset or f899=1) after changing a set point.

Warning

Mandatory

action

Set up “Communication error trip function (c100 to c103 and c523)” to stop the
inverter when EtherNet/IP™ - Modbus® TCP communication is deactivated.

When the parameters are changed, please reset

(power supply reset or f899=1)

the

inverter for the changes to take effect.