Toshiba Tosvert EtherNet/IP - Modbus TCP option IPE002Z User Manual

Page 51

Advertising
background image

E6581741

- 50 -

Examples of Instance 101/151

Access the inverter parameter is enabled using byte 4 to 6 of this Instance.
Set the communication number of the parameter to byte 4, 5 (Index), and the value to byte 6, 7 (Data).

c Read the parameter cmod (Command mode selection, communication number is 0003).

Instance

Byte 15 14 13 12 11 10 9

8

7

6

5

4

3 2 1 0

Hex.

5, 4

0

0

0

0

0

0 0 0 0

0

0

0

0

0

1 1

0x0003

Output Instance 101

7, 6

-

-

-

-

-

-

- -

-

-

-

-

-

-

-

-

-

Input Instance 151

5, 4

0 0 0

0

0

0 0 0 0

0

0

0

0

0

1 1

0x0003

(cmod is 0.)

7, 6

0

0

0

0

0

0 0 0 0

0

0

0

0

0

0

0

0x0000

d Read the parameter f268 (Initial value of UP/DOWN frequency).

Instance

Byte 15 14 13 12 11 10 9

8

7

6

5

4

3 2 1 0

Hex.

5, 4

0

0

0

0

0

0 1 0 0 1

1

0

1

0 0 0 0x0268

Output Instance 101

7, 6

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Input Instance 151

5, 4

0 0 0

0

0

0 1 0 0 1

1

0

1

0 0 0 0x0268

(f268 is 60.0Hz.)

7, 6

0 0 0

1

0

1

1

1

0 1

1

1

0 0 0 0 0x1770

3 Write “60 (Hz)” to the parameter sr1 (Preset speed 1, communication number is 0018).

Instance

Byte 15 14 13 12 11 10 9

8

7

6

5

4

3 2 1 0

Hex.

5, 4

1

0

0

0

0

0 0 0 0 0

0

1

1

0 0 0 0x8018

Output Instance 101

7,

6 0 0 0

1

0

1

1

1

0 1

1

1

0 0 0 0 0x1770

5, 4

1

0

0

0

0

0 0 0 0 0

0

1

1

0 0 0 0x8018

Input Instance 151 (OK)

7,

6 0 0 0

1

0

1

1

1

0 1

1

1

0 0 0 0 0x1770

Input Instance 151 (NG)

5, 4

1 1

0

0

0

0 0 0 0 0

0

1

1

0 0 0 0xC018

(Error code *)

7, 6

0 0 0

1

0

0 0 1 0 0

0

0

0 0 0 0 0x1100

*Data of "Error code"

0x1100: Data out of range
0x1101: Bad address