E6581741

- 8 -

Title

Communi

cation No.

Function Description

Factory

setting

c021

C021

Scanner output 1 address (*3)

0: -

1: fd01 (Status information 1)

2: fd00 (Output frequency, 0.01Hz)

3: fd03 (Output current, 0.01%)

4: fd05 (Output voltage, 0.01%)

5: fc91 (Alarm information)

6: fd22 (PID feedback value, 0.01Hz)

7: fd06 (Input terminal board status)

8: fd07 (Output terminal status)

9: fe36 (VIB input, 0.01%)

10: fe35 (VIA input, 0.01%)

11: fe37 (VIC input, 0.01%)

12: fd04 (Input voltage (DC detection), 0.01%)

13: fd16 (Estimated speed 0.01Hz)

14: fd18 (Torque, 0.01%)

15: -

16: -

17: -

18: -

19: f880 (Free notes)

20: fd29 (Input power, 0.01kW)

21: fd30 (Output power, 0.01kW)

22: fe14 (Cumulative operation time, hour)

23: fe40 (FM terminal output monitor, 0.01%)

24: -

25: fd20 (Torque current, 0.01%)

26: fd23 (Motor overload factor, 0.01%)

27: fd24 (Drive overload factor, 0.01%)

28: fd25 (PBR overload factor, %)

29: fd26 (Motor load factor, %)

30: fd27 (Drive load factor, %)

31: fe56 (Pulse train input, pps)

32: fe70 (Drive rated current, 0.1A)

33: fe76 (Input Watt-hour, 0.1kWh 10

f749

)

34: fe77 (Output Watt-hour, 0.1kWh 10

f749

)

35: fd83 (IGBT temperature, degree C)

1

c022

C022

Scanner output 2 address (*3)

0-35 (Same as c021)

2

c023

C023

Scanner output 3 address (*3)

0-35 (Same as c021)

0

c024

C024

Scanner output 4 address (*3)

0-35 (Same as c021)

0

c025

C025

Scanner output 5 address (*3)

0-35 (Same as c021)

0

c026

C026

Scanner output 6 address (*3)

0-35 (Same as c021)

0

c081-

c096

C081-

C096

Device Name 1-16 (*4)

16 characters
The device name is required if the card uses
DHCP to obtain its IP Address.
Refer to " 3.2.1 Device name (c081-c096) for the
details.

0,0,0,0,

0,0,0,0

c100

C100

Communication error
detection delay time

0.0 - 100.0 sec.

0.0

c101

C101

Inverter operation at the
communication loss action

0: Stop and controlled by cmod, fmod
1: Operation continue
2: Deceleration stop
3: Coast stop
4: Network error stop (err8 trip)
5: Preset speed operation (by c102 setting)

4

c102

C102

Preset speed operation
selection

0: None
1 to 15: Preset speed

0

c103

C103

Communication time-out
condition selection

0: Disconnection detection
1: When communication mode enable (Both

cmod

and fmod are set CANopen or

communication option) only

2: 1 + Driving operation

0

(*3): This parameter is effective by reset. Please reset (power supply reset or f899=1) after changing a set point.
(*4): (V[R) does not work for this parameter.