Attribute 5

State Descriptions


Adapted from document [CIP] “

THE CIP NETWORKS LIBRARY

Bit

Called

Definition

0 Owned

TRUE indicates the device (or an object within the device) has an owner.
Within the Master/Slave paradigm the setting of this bit means that the
Predefined Master/Slave Connection Set has been allocated to a master.
Outside the Master/Slave paradigm the meaning of this bit is TBD.
Æ unsupporteed

1 -

(System

reserved)

2 Configured.

TRUE indicates the application of the device has been configured to do
something different than the “out–of–box” default. This shall not include
configuration of the communications.

3 -

(System

reserved)

0000

Self-Testing or unknown

0001

Firmware update in progress

0010

At least one faulted I/O connection

0011

No I/O connections established

0100

Non-Volatile configuration bad

0101

Major Fault – either bit 10 or bit 11 is true (1)

0110

At least one I/O connection in run mode

0111

At least one I/O connection established, all in idle mode

4-7

Extended Device
Status

1000-
1111

Unused

8

Minor Recoverable
Fault

TRUE indicates the device detected a problem with itself, which is thought to
be recoverable. The problem does not cause the device to go into one of the
faulted states.

9

Minor
Unrecoverable
Fault.

TRUE indicates the device detected a problem with itself, which is thought to
be unrecoverable. The problem does not cause the device to go into one of
the faulted states.

10

Major Recoverable
Fault.

TRUE indicates the device detected a problem with itself, which caused the
device to go into the “Major Recoverable Fault” state.

11

Major
Unrecoverable Fault

TRUE indicates the device detected a problem with itself, which caused the
device to go into the “Major Unrecoverable Fault” state.

12-15 - (System

reserved)

Note: Don’t use the “System reserved” bit and Bit0 for the judgement.