Toshiba Tosvert EtherNet/IP - Modbus TCP option IPE002Z User Manual

Page 49

Advertising
background image

E6581741

- 48 -

Examples of Instance 100/150

Stop

Instance

Byte 15 14 13 12 11 10 9

8

7

6

5

4

3 2 1 0

Hex.

1, 0

0

0

0

0

0

0 0 0 0 0

0

0

0

0

0

0

0x0000

Output Instance 100

3, 2

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

1, 0

0 1 0

0

1

0 0 0 0 0

0

0

0 0 0 0 0x4800

Input Instance 150

3, 2

0

0

0

0

0

0 0 0 0 0

0

0

0

0

0

0

0x0000

Forward running 60Hz

Instance

Byte 15 14 13 12 11 10 9

8

7

6

5

4

3 2 1 0

Hex.

1, 0

1 1

0

0

0

1

0 0 0 0

0

0

0 0 0 0 0xC400

Output Instance 100

3,

2

0 0 0

1

0

1

1

1

0 1

1

1

0 0 0 0 0x1770

1, 0

0 1 1

0

0

1

0 0 0 0

0

0

0 0 0 0 0x6400

Input Instance 150

3,

2

0 0 0

1

0

1

1

1

0 1

1

1

0 0 0 0 0x1770

Reverse running 60Hz

Instance

Byte 15 14 13 12 11 10 9

8

7

6

5

4

3 2 1 0

Hex.

1, 0

1 1

0

0

0

1

1

0 0 0

0

0

0 0 0 0 0xC600

Output Instance 100

3,

2

0 0 0

1

0

1

1

1

0 1

1

1

0 0 0 0 0x1770

1, 0

0 1 1

0

0

1

1

0 0 0

0

0

0 0 0 0 0x6600

Input Instance 150

3,

2

0 0 0

1

0

1

1

1

0 1

1

1

0 0 0 0 0x1770

Preset speed 1 with forward running (sr1)

Instance

Byte 15 14 13 12 11 10 9

8

7

6

5

4

3 2 1 0

Hex.

1, 0

1

0

0

0

0

1

0 0 0 0

0

0

0 0 0 1

0x8401

Output Instance 100

3, 2

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Input Instance 150

1, 0

0 1 1

0

0

1

0 0 0 0

0

0

0 0 0 0 0x6400

(sr1 is set 5Hz.)

3, 2

0

0

0

0

0

0 0 1 1 1

1

1

0 1 0 0 0x01F4

Fault reset *

Instance

Byte 15 14 13 12 11 10 9

8

7

6

5

4

3 2 1 0

Hex.

1, 0

0 0 1

0

0

0 0 0 0 0

0

0

0 0 0 0 0x2000

Output Instance 100

3, 2

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-


About the other command, refer to section 3.2.4.2.

* Fault reset works only 1 time when 0 -> 1.

Advertising