IV. a - REFRIGERATORS:

Both refrigerators and Freezers do not require manual

defrosting. During normal operation, a refrigerator con-

tinuously circulates above freezing cabinet air through the

coil. A compressor “OFF” cycle occurs every 2 1/2 Hours

for 20 minutes to melt any frost which may accumulate

on the coil during the compressor “ON” cycle. The control

will read “dEF” and the green water drop will be illumi-

nated. With standard holding refrigerators, high relative

humidity is also maintained to prevent dehydration of

stored product.

IV. b - FREEZERS:

During normal operation, a freezer continuously circu-

lates below freezing cabinet air through the coil. The

coil requires a periodic defrosting for proper operation.

This is accomplished by an automatic, time activated,

temperature/time terminated, defrost program, utilizing

hot gas from the refrigeration system. The controller is

preset at the factory for six equally spaced defrost cycles

within each 24-hour period.

At the start of a freezer defrost cycle, the compressor,

condenser fan and evaporator fan shut off. The hot gas

relay will be energized, this will energize the hot gas

solenoid valve thru the normally open contacts and the

condenser fan circuit will be de-energized thru the (nor-

mally closed contacts), and the compressor will restart.

When the evaporator coil sensor reaches 40

0

F the coil is

fully defrosted or if the maximum time of defrost dura-

tion (20 minutes) is reached (which ever comes first) then

the defrost hot gas relay is de-energized. The condenser

fan restarts and the hot gas solenoid valve closes, The

compressor system returns to the cooling mode. Total

refrigeration system operation is then resumed (green

snowflake icon goes out) and the display will show def

for an additional 10 minutes then return to reading the

inside cabinet temperature. The evaporator fan(s) are

delayed from starting at the termination of the defrost

cycle and will automatically resume by time or temp delay

(5 minutes or 30

0

F coil sensor temperature, whichever

comes first ).

IV. b - FREEZERS (continued):

During freezer defrost operation, heat is confined to the

coil enclosure to prevent any significant rise in tempera-

ture within the food zone. The fan delay control function

upon termination of a defrost cycle is two-fold. First, to

prevent blowing warm air into the food storage area.

Second, to prevent any condensation on the defrost coil

from being blown into the food storage area.

The microprocessor control is set from the factory to termi-

nated defrost at 20 minutes in the event of sensor failure.

This setting should never be tampered with, without first
consulting Traulsen’s Technical Service department.

V. a - CLEANING THE CONDENSER/FILTER:

The most important thing you can do to insure a long,

reliable service life for your Traulsen is to regularly clean

the condenser coil and or filter if provided.

The microprocessor control will notify you through a

“CLN-FIL” message when the condensing temperature of

the refrigerator reaches 140 degrees F or greater. If the

condensing temperature reaches 160 degrees F the com-

pressor will automatically turn off . When the temperature

drops below 140 degrees F the compressor will restart

and when the temperature drops below 120 degrees F

the alarm will reset.

WARNING: DISCONNECT ELECTRICAL POWER SUPPLY

BEFORE CLEANING ANY PARTS OF THE UNIT.

To clean the condenser/filter, first disconnect electrical

power to the cabinet and remove the front louver as-

sembly. To do so, place hands under the louver panel and

pull out and up to get louver panel off bracket of the unit.

See diagram below.

Proceed to vacuum or brush any dirt, lint or dust from

the finned condenser coil/filter, the compressor and other

cooling system parts. If significant dirt is clogging the con-

denser fins or filter, use compressed air to blow this clear.

To replace the louver assembly reverse the process.