7. Communication parameters

The settings of communication-related parameters can be changed from the operation panel and
the external controller (computer). Note that there are two types of parameters: parameters whose
settings take effect immediately after the setting and parameters whose settings do not take effect
until the inverter is turned back on or reset.

Com-

munica-

tion

Number.

Title

Function

Adjustment range

Unit

Default

setting

Valid

Reference

0800



Baud rate
(2-wire RS485)

0: 9600bps
1: 19200bps
2: 38400bps

-

1

After reset.

Section 7.1

0801



Parity (common)

0: Non parity
1: Even parity
2: Odd parity

-

1

After reset.

Section 7.1

0802



Inverter number
(common)

0-247

1

0

Real time

Section 7.2

0803



Communication
time-out time
(common)

0:OFF
1-100s

1s

0

Real time

Section 7.3

2-wire

4-wire

0

-

-

1

t alarm

-

2

Err5 trip

-

3

-

t alarm

4

t alarm

t alarm

5

Err5 trip

t alarm

6

-

Err5 trip

7

t alarm

Err5 trip

0804



Communication
time-out action
(common)

8

Err5 trip

Err5 trip

1

8

Real time

Section 7.3

0805



Send waiting time
(2-wire RS485)

0.00: Default
0.01-2.00s

0.01s

0.00

Real time

Section 7.4

0806



Inverter-to-inverter
communication

(2-

wire RS485)

0:Slave (issues a 0Hz command if some-

thing goes wrong with the master)

1:Slave (continues operation if something

goes wrong with the master)

2:Slave (trips for emergency stop if

something goes wrong with the master)

3:Master (sends a frequency command)
4:Master (sends an output frequency)
5.Master (sends a torque command)
6.Master (sends an output torque com-

mand)

-

0

After reset.

Chapter 6

0807



Protocol selection
(2-wire RS485)

0: TOSHIBA
1:MODBUS-RTU

-

0

After reset.

Chapter 3

0810



Frequency point
selection

0:Disabled
1:2-wire RS485
2:4-wire RS485
3:Communication add option

-

0

Real time

Section 6.1

0811



Point 1 setting

0-100%

-

0

Real time

0812



Point 1 frequency

0-Hz

0.01Hz

0.0

Real time

0813



Point 2 setting

0-100%

-

100

Real time

0814



Point 2 frequency

0-Hz

0.01Hz

60.0

Real time

Section 6.1

0820



Communication
speed
(4-wire RS485)

0: 9600bps
1: 19200bps
2: 38400bps

-

1

After reset.

Section 7.1

0825



Send waiting time
(4-wire RS485)

0.00: Normal
0.01-2.00s

0.01s

0.00

Real time

Section 7.4